esera automation 11229 V2 사용자 설명서 - 페이지 3
{카테고리_이름} esera automation 11229 V2에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. esera automation 11229 V2 6 페이지. 8-fold digital output / switching module / binary output 8 x 8a for 1-wire bus system w/auto-e-connect
Art. No. 11229 V2
6
Connection plan
The connection plan is available in our web shop
as a separate document.
Note: A back-up fuse must be provided for
terminal 14 with 10A.
Connection module top side:
14 = Current input
15 = Output 1, make-contact
16 = Output 2, make-contact
17 = Output 3, make-contact
18 = Output 4, make-contact
19 = Output 5, make-contact
20 = Output 6, make-contact
21 = Output 7, make-contact
22 = Output 8, make-contact
Module bottom side:
1-Wire Bus
10 = +12V external voltage* (optional)
11 = GND (ground)
12 = 1-Wire data line
13 = +12V voltage
* If the Bus system is not able to supply the module
with sufficient power, an external 12V power supply
can be connected as support.
This power supply unit must not be used to supply
non-Bus modules.
7
Conformity
EN 50090-2-2,
EN 61000-4-2, ESD
EN 61000-4-3, HF
EN 61000-4-4, Burst
EN 61000-4-5, Surge
EN 61000-6-1, Fault-free operation
EN 61000-6-3, Stray radiations
RoHS
8
Operation mode, display
After the device has been put into operation, all LEDs of the relay outputs will light up briefly. From this moment
on, the 8-fold switch module is ready for operation and switching commands can be sent via the 1-wire interface.
The corresponding status LEDs of the active relays will light up.
Display
Designation
LED 1-8
Output 1-8
LED PWR
Power
LED Status
Status display
All rights reserved. Reproduction as well as electronic duplication of this user guide, complete or in part, requires the written consent of
ESERA GmbH. Errors and technical modification subject to change. ESERA GmbH, ESERA-Automation 2020
www.esera.de
LED function
- LED lights up for 2 seconds to start the system
- LED indicator lights up when the respective output is active
- LED flashing lights up 2 seconds to start the system
- LED display for operational readiness
- LED lights up for 2 seconds to start the system
- Flashes when controlled via the bus interface
11229V2 V2.0 R1.0 Manual