ESI ES2247B 사용자 지침 - 페이지 7
{카테고리_이름} ESI ES2247B에 대한 사용자 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. ESI ES2247B 20 페이지. 2 channel multi-purpose
programmer
ESI ES2247B에 대해서도 마찬가지입니다: 설치 지침 매뉴얼 (16 페이지)
the lifetime of the programmer and the clock is automatically
put forward 1 hour at 1:00am on the last Sunday of March
and back 1 hour at 2:00am on the last Sunday of October.
The clock is factory pre-set to UK time and date, but you can
alter it if you want. During installation, the installer selects 24
hour, 5/2 day, or 7 day programming and either 2 or 3 on/
off periods per day, via the Technical Settings (see installation
instructions).
The large, easy to read display makes programming easy and
the unit is designed to eliminate the possibility of accidental
changes to your programme. Buttons normally visible, only
affect your set programme temporarily. All buttons which can
permanently change your programme are located behind the
flip over facia.
- The 24 hour programmer option runs the same
programme every day.
- The 5/2 Day programmer option allows different ON/OFF
times at weekends.
- The 7 Day programmer option allows different ON/OFF
times for each day of the week.
- Pumped System (PU) allows independent control of
Central Heating and Hot Water.
- Gravity System (Gr) does not allow Central Heating
without Hot Water but can provide Hot Water without
Central Heating.
N.B. When 5/2, 7 day or 24hr is selected for HW then the
same will be applied to Heating and vise versa
IMPORTANT: This programmer is not suitable for the
switching of devices greater than 6Amp rated. (e.g. Not
suitable for use as an immersion timer)
7