Instrument XR80D shall be
mounted on a DIN rail.
The
temperature
range
allowed for correct operation
is 0÷60 °C. Avoid places
subject to strong vibrations,
corrosive gases, excessive
dirt or humidity. The same
recommendations apply to
probes. Let air circulate by the
cooling holes.
9. ELECTRICAL CONNECTIONS
The instrument is provided with screw terminal block to connect cables with a cross
section up to 2,5 mm
. Before connecting cables make sure the power supply complies
2
with the instrument's requirements. Separate the probe cables from the power supply
cables, from the outputs and the power connections. Do not exceed the maximum current
allowed on each relay, in case of heavier loads use a suitable external relay.
9.1 PROBE CONNECTION
The probes shall be mounted with the bulb upwards to prevent damages due to casual
liquid infiltration.
10. HOW TO USE THE HOT KEY
10.1 HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD)
1.
Program one controller with the front keypad.
When the controller is ON, insert the "Hot key" and push o key; the "uPL"
2.
message appears followed a by flashing "End"
3.
Push "SET" key and the End will stop flashing.
4.
Turn OFF the instrument remove the "Hot Key", then turn it ON again.
NOTE: the "Err" message is displayed for failed programming. In this case push again o
key if you want to restart the upload again or remove the "Hot key" to abort the operation.
10.2 HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY (DOWNLOAD)
1.
Turn OFF the instrument.
2.
Insert a programmed "Hot Key" into the 5 PIN receptacle and then turn the
Controller ON.
3.
Automatically the parameter list of the "Hot Key" is downloaded into the Controller
memory, the "doL" message is blinking followed a by flashing "End".
4.
After 10 seconds the instrument will restart working with the new parameters.
5.
Remove the "Hot Key"..
NOTE the message "Err" is displayed for failed programming. In this case turn the unit off
and then on if you want to restart the download again or remove the "Hot key" to abort the
operation.
11. ALARM SIGNALS
Message
Cause
"EE"
Data or memory failure
"P1"
Probe failure
"HA"
Maximum temp. alarm Output unchanged.
"LA"
Minimum temp. alarm
11.1 ALARM "EE"
The instrument is provided with an internal check verifying memory integrity. Alarm "EE"
flashes when a failure in the internal memory is detected. In such case call the service.
11.2 ALARM RECOVERY
Probe alarm "P1" start some seconds after the fault in the related probe; it automatically
stops some seconds after the probe restarts normal operation. Check connections before
replacing the probe.
Temperature alarms "HA" and "LA" automatically stop as soon as the thermostat
temperature returns to normal values and when defrost starts.
12. TECHNICAL DATA
Housing: self extinguishing ABS.
Case: XR80C frontal 32x74 mm; depth 60mm;
XR80D 4 DIN modules 70x85 mm; depth 61mm
Mounting: XR80C panel mounting in a 71x29mm panel cut-out
XR80D DIN RAIL mounted in a omega (3) din rail
Protection: IP20;
Frontal protection: XR80C IP65 with frontal gasket RG-C (optional).
Connections: Screw terminal block ≤ 2,5 mm
1592007271 XR80C-D GB r1.0 20.05.2005.doc
Installing and Operating Instructions
Output
Output according to par. "Con" and "COF"
Output unchanged.
wiring.
2
Power supply: according to the model: 12Vac/dc, ±10%; 24Vac/dc, ±10%; 230Vac
±10%, 50/60Hz, 110Vac ±10%, 50/60Hz
Power absorption: 3VA max
Display: 3 digits, red LED, 14,2 mm high; Inputs: 1 PTC or NTC probe.
Relay outputs: compressor SPST relay 8(3) A, 250Vac or SPST relay 20(8)A; 250Vac
agitator: SPDT relay 8(3) A, 250Vac or
Kind of action: 1B; Pollution grade: normal; Software class: A.
Data storing: on the non-volatile memory (EEPROM).
Operating temperature: 0÷60 °C; Storage temperature: -30÷85 °C.
Relative humidity: 20÷85% (no condensing)
Measuring and regulation range: PTC probe: -50÷150°C (-58÷302°F)
NTC probe: -40÷110°C (-58÷230°F)
Resolution: 0,1 °C or 1°C or 1 °F (selectable).
Accuracy (ambient temp. 25°C): ±0,7 °C ±1 digit
13. CONNECTIONS
13.1 XR80C: COMPRESSOR 8A
8(3)A250V
1 2 3 4 5
Line
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.
13.2 XR80C: COMPRESSOR 20A
8(3)A250V
1 2 3 4 5
Line
12Vac/dc supply: connect to the terminals 7 and 8.
24Vac/dc supply: connect to the terminals 7 and 8.
120Vac supply: connect to the terminals 7 and 8.
13.3 XR80D: 8A COMPRESSOR
Line
24Vac/dc supply: connect to the terminals 11 and 12.
120Vac supply: connect to the terminals 11 and 12.
230Vac supply: connect to the terminals 11 and 12.
XR80C – XR80D
9 10
8(3)A250V
6
7
8
Hot Key
N.C.
Comp
9 10
20(8)A250V
6
7
8
Hot Key
N.C.
Comp
3
4
8(3)A/250Vac
8(3)A/250Vac
13 14 15 16 17 18 19
n.c.
n.c.
Comp
R1.0 1592007271
11 12
11 12
Power
Supply
230Vac
11 12