EDI NSM-3E 운영 매뉴얼 - 페이지 14

{카테고리_이름} EDI NSM-3E에 대한 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. EDI NSM-3E 16 페이지. Enhanced signal monitor

5.1 ELECTRICAL

5.1.1 POWER REQUIREMENTS

Operating Line Voltage .......................................................................... 75 to 135 VAC RMS
Operating Line Frequency ..................................................................................... 60 +_3Hz
Power Consumption ......................................................................................... 5W (nominal)

5.1.2 AC VOLTAGE MONITORS (POSITIVE OR NEGATIVE HALF WAVE INPUT)

Green Signal Inputs
Yellow signal Inputs
Walk Signal Inputs
Red Signal Inputs
Red Enable Input
®
LEDguard
Low Threshold Signal Inputs
®
LEDguard
High Threshold Signal Inputs
AC Line Voltage Monitor

5.1.3 DC VOLTAGE MONITOR

+24 VDC Inputs

5.1.4 LOGIC INPUTS

Controller Voltage Monitor, External Reset, +24V Monitor Inhibit

5.2 TIMING FUNCTIONS

Conflict
Eberle Design Inc.
NSM-3E Signal Monitor Unit
Operations Manual
Section 5
Specifications
No Detect .................................................. less than 15 Vrms
Detect .................................................. greater than 25 Vrms
No Detect .................................................. less than 15 Vrms
Detect .................................................. greater than 25 Vrms
No Detect .................................................. less than 15 Vrms
Detect .................................................. greater than 25 Vrms
No Detect .................................................. less than 50 Vrms
Detect .................................................. greater than 70 Vrms
No Detect .................................................. less than 50 Vrms
Detect .................................................. greater than 70 Vrms
No Detect .................................................. less than 15 Vrms
Detect .................................................. greater than 25 Vrms
No Detect .................................................. less than 50 Vrms
Detect .................................................. greater than 70 Vrms
Drop-out ............................................. less than 92 +_2 Vrms
Restore ..........................................greater than 96 +_2 Vrms
Inactive ..................................................... less than +18 Vdc
Active ....................................................greater than +22 Vdc
Active .......................................................... less than +8 Vdc
Inactive .................................................greater than +16 Vdc
No Fault ....................................... less than 200 milliseconds
Fault ......................................... greater than 450 milliseconds
Typical ........................................................ 350 milliseconds
Page 10