AIMS Power PRM1000W12120S 운영 매뉴얼 - 페이지 12

{카테고리_이름} AIMS Power PRM1000W12120S에 대한 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AIMS Power PRM1000W12120S 16 페이지. 1u rack

AIMS Power PRM1000W12120S 운영 매뉴얼

Operating Procedure

A. Verify the battery operating voltage and protection switch is on (inverter off).
B. Tum protection switch "off "(circuit breaker) once the battery connection has been verified.
C. The length of the cable may vary slightly, but should preferably be less than 10 Ft. The shorter the lenght of the cable the better the
batteries will perform.
If a longer distance is needed, a larger gauge cable is required.
minimum cable size recommendations : 12Vdc / 4Awg, 24Vdc / 6Awg, 48Vdc / 8Awg
D. Connect the Red cable lug to the positive
Arrange the battery cables to the safest angles. Turn inverter on and confirm inverter is operating properly.
E. Turn protection switch "off " If the buzzer is sounding, turn the connected AC devices off and toggle the power switch off then on.
The buzzer should stop.
F. Now you should connect and turn the AC devices on. Most equipment using motors, have a higher startup requirement.
This may cause the inverter to buzz and go into overload or pop the circuit breakers. This should not damage the inverter;
however you should not continue to try and power up the equipment. Repeated overloads will cause damage to the inverter Call
AlMS Power Tech support and verify startup requirements.
G. The frequency of the inverter is fine-tuned at 60Hz from the manufacture.
H. The inverter may operate in overload for a short period of time. If you continue the use in overload, the inverter may overheat and
shut down. You will then be required to turn the inverter off and on again.
12
on the battery and Black lug to the negative
of the battery.