Unit should be tested at least once a year for the proper operation as follows:
Output Voltage Test:
Battery Test:
Note:
Note:
Terminal Legend
AC/AC
– DC +
– BAT +
AC FAIL
NC, C, NO
LOW BAT
NC, C, NO
16.5VAC, 20VA
Plug-in Transformer
(UL Listed Class 2
Transformer)
750mA 12VDC
Power-Limited Output
Stand-by
Battery
AL100UL Installation Guide
Maintenance:
Under normal load conditions the DC output voltage should be checked for proper
voltage level (Stand-by Specifications Chart).
Under normal load conditions check that the battery is fully charged, check specified
voltage both at the battery terminal and at the board terminals marked [– BAT +] to
ensure that there is no break in the battery connection wires.
Maximum charging current under discharge is 500mA.
Expected battery life is 5 years; however, it is recommended changing batteries in
4 years or less if needed.
Terminal Identification:
Function/Description
Low voltage AC input (16.5VAC/20VA). UL Listed. Class 2 plug-in transformer.
12VDC @ 750mA continuous power-limited output.
Stand-by battery connections. Maximum charge rate 500mA.
Indicates loss of AC, e.g. connect audible device or alarm panel. Relay is normally
energized when AC power is present. Contact rating 1A @ 28VDC.
Indicates low battery condition e.g connect audible device or alarm panel.
Relay is normally energized. Contact rating 1A @ 28VDC.
AC
Class 2
Output
DC
C1
IC1
PTC1
Fig. 1
RL2
RL1
- 3 -