Arthur Grillo DPC200-R 설치 및 운영 매뉴얼 - 페이지 10

{카테고리_이름} Arthur Grillo DPC200-R에 대한 설치 및 운영 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Arthur Grillo DPC200-R 16 페이지. Airflow / pressure controller

Arthur Grillo DPC200-R 설치 및 운영 매뉴얼
OPERATION

5.3 Measuring mode

Display
ΔP Measurement
200 Pa
menu
unit metric
operating mode
control mode
parameter
diff. pressure
limit switch
150 Pa
alarm delay time
back and confirm
fan k-factor
k = 70
limit switch
300 m³/h
alarm delay time
back and confirm
5.4 Control mode
Display
ΔP Measurement
200 Pa
menu
10
Start menu: Press button T1 approx. two seconds
Press button T2 to get to the next menu item
Press button T1 to switch between:
[Pa] and [m
/h] <=> [InH
3
Press button T2 to get to the next menu item
Press button T1 to switch between:
measuring mode <=> control mode
Press button T2 to get to the next menu item
Press button T1 to switch between:
diff. pressure <=> volume flow
Press button T2 to get to the next menu item
If selected parameter = diff. pressure
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Switching delay time adjustment range:
1...60 seconds or 2....15 minutes
Press button T1 to leave the menu
Press button T2 to stay in the menu
If selected parameter = volume flow
than follows the additional input for the k-factor
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Button T1: reset value
Button T2: set value
Button T1: confirm value, display flashes once
Press button T2 to get to the next menu item
Switching delay time adjustment range:
1...60 seconds or 2....15 minutes
Press button T1 to leave the menu
Press button T2 to stay in the menu
Start menu: Press button T1 approx. two seconds
Press button T2 to get to the next menu item
Doc.-no.: DPC200-R_02_EN
Action
O] and [l/s]
2
Action
Issue: 06/2018