INSTALLATION

3.
Installation
The differential pressure sensor DS200 has to be mounted vertically, to assure the accuracy.
The connection of the pressure lines is done by plastic tubes with an internal
CAUTION
NOTICE

3.1 Dimensions

All dimensions in mm.

3.2 Wall mounting

1.
Hold the DS200 against the wall. Mark the mounting holes.
2.
Drill mounting holes for properly sized screws.
3.
Put the screws through the housing mounting holes.
4.
Tighten screws.
6
Material damage
Read the manual carefully before installation and operation
Only experienced stuff may connect the device and bring it into
operation.
The device is position depended.
The DS200 must be mounted vertically
The DS200 can be attached to a wall.
Doc.-no.: DS200_01_EN
Issue: 05/2017