Power Supply Specifications:
AC Input:
Output:
Battery:
Stand-by/Alarm Current Consumption:
EOL Resistor (end of line):
Stand-by Specifications:
Stand-by Batteries
24VDC/12AH
(use two (2) 12VDC batteries in series)
24VDC/7AH
24VDC/36AH Battery
12VDC/36AH Battery
Note: Unit is equipped with two (2) 1 amp max. auxiliary outputs: "AUX1" will automatically disconnect when
AC is lost. "AUX2" will remain battery backed up during power outage. For loads connected to "AUX2" please,
refer to battery "Stand-by Specifications" above for ratings. When loads are connected to the "AUX1" and or
"AUX2" outputs during alarm condition, the remaining outputs may, not exceed 10 amp total alarm current.
(example: AUX1 = 1 amp, AUX2 = 1 amp, outputs up to 8 amp).
Installation Instructions:
Wiring methods shall be in accordance with the National Electrical Code/NFPA 70/NFPA 72/ANSI, and with all local
codes and authorities having jurisdiction. Product is intended for indoor use only.
1. Mount unit in desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the
enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure's
upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the
enclosure. Drill the lower holes and install the three fasteners. Place the enclosure's upper keyholes over the two
upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 10).
Secure enclosure to earth ground.
Carefully review:
Application Guide (for AL642UL2ADA, AL842UL2ADA, AL1042UL2ADA)
Power Supply Specifications
Stand-by Specifications
Output Programming Selection Table
Sync Mode Selection Table
Terminal Identification Table
LED Status Indication Table
2. Connect green lead to earth ground (Fig 1).
Connect the line (L), ground (G), and neutral (N) terminals to a separate unswitched
AC circuit (115VAC, 60Hz) dedicated to the Fire Alarm System.
3. Measure output voltage before connecting devices.This helps avoid potential damage.
4. Connect battery to terminals marked [+ BAT - -] on the Power Supply Board (battery leads included).
Use two (2) 12VDC batteries connected in series.
5. Set output selection switches marked [OUT1 through OUT4] to follow corresponding input [IN1 & IN2]
and desired output signal type (Output Programming Selection Table, pg. 4).
6. Connect FACP output to desired AL842LGK logic board inputs, and notification appliances to desired AL842LGK
logic board outputs (see Application Guide).
Note: The 2-wire horn/strobe sync mode will only synchronize horns, horn strobes, strobes with
synchronization capability.
7. For connection of smoke detectors, digital dialer (Optional Hookup Diagram, pg. 7).
8. To enable ground fault detection remove insulating washer between the board and stand-off (Fig. 2, A/B, pg. 7).
9. Separation of power limited wiring from non-power limited wiring must be at least 1/4".
AL1042UL2ADA
115VAC / 4.4 amp @ 60Hz.
24VDC. Maximum 2.5 amp per output.
Total of 10 amp in Alarm Condition (see note below).
For 24VDC operation use two (2) 12VDC batteries connected in series.
90mA/175mA
2.2K (2200 ohm).
Stand-by
Alarm Output
Time
Total Amp/Minutes Output Current Alarm Current
24 Hours
10 amp/15 Minutes
60 Hours
10 amp/5 Minutes
24 Hours
10 amp/5 Minutes
24 Hours
10 amp/15 Minutes
24 Hours
10 amp/15 Minutes
(pg. 3)
(pg. 3)
(pg. 4)
(pg. 4)
(pg. 5)
(pg. 6)
Aux 2 Stand-by
50mA
-
-
1 amp
1 amp
L
line
ground
Aux 2
1 amp
1 amp
1 amp
1 amp
1 amp
G
N
neutral
Fig. 1