Note: Unit is equipped with two (2) 1 amp max. auxiliary outputs: "AUX1" will automatically disconnect when
AC is lost. "AUX2" will remain battery backed up during power outage. For loads connected to "AUX2" please,
refer to battery "Stand-by Specifications" pg. 3 for ratings. When loads are connected to the "AUX1" and or
"AUX2" outputs during alarm condition, the remaining outputs may, not exceed 6.5 amp total alarm current.
(example: AUX1 = 1 amp, AUX2 = 1 amp, outputs up to 6.5 amp).
AL600ADA - Power Supply Board
Terminal Legend Function/Description
L, G, N
Connect 120VAC to these terminals: L to Hot, N to Neutral, G to ground.
-- DC +
24VDC @ 6.5 amp in alarm non-power limited output.
Form "C" dry contacts indicate the loss of AC, with AC present terminals marked [NO and C]
AC FAIL
are open, [NC and C] are closed. When loss of AC occurs terminals marked [NO and C] are closed,
NO, C, NC
[NC and C] are open.
Form "C" dry contacts used to instantaneously signal the loss AC to local annunciation devices, with
AC LOCAL
AC present terminals marked [NO and C] are open, [NC and C] are closed. When loss of AC occurs
NC, NO, C
terminals marked [NO and C] are closed, [NC and C] are open.
Form "C" dry contacts indicate low battery voltage or loss of battery voltage. Under normal
BAT FAIL
conditions terminals marked [N.O. and C] are open, [NC and C] are closed. During a trouble
NO, C, NC
condition terminals marked [N.O. and C] are closed, and [N.C. and C] are open (Fig. 2, pg. 7).
+ BAT --
Stand-by battery input (leads provided) (Fig. 2, pg. 7).
*Power Board Parameter Specifications:
• AC Fail condition will report approximately 30 seconds after loss of AC. To delay report for 2.5 to 3 hours cut
jumper AC DELAY on the Power Supply Board (AC trouble output delay option). If this mode is selected the Power
Supply Board must be reset by removing all power to it for 30 seconds.
• Low battery condition will report at approximately 21VDC.
• Battery presence detection will report with in 180 seconds after battery remains undetected (missing or removed).
A restored battery will report within 30 seconds.
AL600ADA - Power Supply Board
Red (DC)
Green (AC)
ON
ON
ON
OFF
OFF
ON
OFF
OFF
AL842LGK - Logic Board
LED
OFF
ON
Normal
ON
Normal
OFF
Normal
OFF
Normal
Input 1
Normal
Input 2
Normal
Fault
Normal
- 6 -
Terminal Identification Table:
LED Diagnostics:
Power Supply Status
Normal operating condition.
Loss of AC, Stand-by battery supplying power.
No DC output.
Loss of AC. Discharged or no stand-by battery. No DC output.
ON
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
Alarm Condition
BLINK (LONG)*
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
Trouble Condition
---
BLINK (SHORT)**
Trouble Condition Memory
Trouble Condition Memory
Trouble Condition Memory
Trouble Condition Memory
---
---
---
AL642ULADA