AKO AKOCAM AKO-156331 매뉴얼
{카테고리_이름} AKO AKOCAM AKO-156331에 대한 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. AKO AKOCAM AKO-156331 4 페이지.
1561H302 Ed.04
GB
Temperature controller AKOCAM
AKOCAM is a solution for static or ventilated cold room stores.
It directly controls single-phase units with compressors of up to 2 PH.
These models control and record the temperature.
Depending on the model, they also have: A printer for printing data or graphs. An alarm for
persons trapped inside, with an optical acoustic alarm, and a lamp for requesting help.
AKO-15613
AKO-156131
AKO-15633
AKO-156331
1- Versions and references
MODEL
PRINTER
ALARM
AKO-15613
NO
NO
AKO-156131
YES
NO
AKO-15633
NO
NO
AKO-156331
YES
NO
NO
YES
AKO-156332
2- Technical data
Temperature range. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -40.0 ºC to +99.9 ºC
Resolution, Set Point and differential . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0,1 ºC
Thermometric accuracy. . . . . . . . . . . . . . . . . . . . . . ± 1 ºC s/ EN 12830 and EN 13485
Denomination . . . . EN 12830, S, A, 1, -40 ºC +40 ºC; EN 13485, S, A, 1, -40 ºC +40 ºC
Probe tolerance at 25 ºC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ± 0,4 ºC
Input for probe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . AKO-149XX
Maximum input power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 VA
Working ambient temperature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 ºC to 50 ºC
Storage ambient temperature. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . -30 ºC to 70 ºC
Installation category: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II under EN 61010-1
Pollution degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . II under EN 61010-1
Double insulation between the power supply, the secondary circuit and the relay output.
Recorder autonomy in the event of a power failure . . . . . . . . . . . . . . . . . . . . 48 Hours
Alarm autonomy in the event of a power failure. . . . . . . . . . . . . . . . . . . . . . . 10 Hours
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Li-Polymer for recorder
Internal buzzer
3- Installation
The controller should be installed in a place protected from vibrations, water and corrosive gases,
and where ambient temperature does not surpass the value specified in the technical data.
In order for the controllers to have IP65 protection degree, the gasket should be properly
installed between the apparatus and the perimeter of the panel cut-out where it is to be fitted.
In order to give a correct reading, the probe should be installed in a place without heat
influences other than the temperature that is to be measured or controlled.
AKO-156332
CONTROL RELAYS
POWER SUPPLY
(250V, cos j
=1)
Cool:
16 A SPST
230 V~ +10% -15%
Light:
16 A SPST
50/60 Hz ± 3 Hz
Alarm:
8 A SPDT
Cool:
16 A SPST
100 - 240 V~
Light:
16 A SPST
50/60 Hz ± 3 Hz
Alarm:
8 A SPDT
Cool:
16 A SPST
Def:
16 A SPST
230 V~ +10% -15%
Fan:
8 A SPDT
Light:
16 A SPST
50/60 Hz ± 3 Hz
Alarm:
8 A SPDT
Aux:
16 A SPST
Cool:
16 A SPST
Def:
16 A SPST
Fan:
8 A SPDT
100 - 240 V~
Light:
16 A SPST
50/60 Hz ± 3 Hz
Alarm:
8 A SPDT
Aux:
16 A SPST
Cool:
16 A SPST
Def:
16 A SPST
Fan:
8 A SPDT
230 V~ +10% -15%
Light:
16 A SPST
50/60 Hz ± 3 Hz
Alarm:
8 A SPDT
Aux:
16 A SPST
3.1 Wall mounting
- Remove cover T from the equipment (Fig.1a or Fig. 1b).
- Open the equipment and separate the front part of the housing (Fig.2).
- Drill the holes for the glands that are necessary for the cables to pass through, guided by
the pre-cut centres on the sides of the housing.
- Drill 3 holes for anchoring the housing at the centres indicated 1, 2, 3 (Fig.3a or 3b).
- Drill 3 holes in the wall, in accordance with the anchoring holes made previously in the
equipment.
- Anchor the glands to the equipment.
- Insert and tighten the 3 screws+plug through the housing, on the 3 holes drilled in the
wall.
- Insert the cables into the glands.
- Mount the front part on the housing (Fig.2).
- Insert and tighten screws D, E, F (Fig.1a or Fig. 1b)
- After connecting the cables based on the connection diagram, close cover T, insert and
tighten screws A, B, C (Fig.1a or Fig.1b).
3.2 Panel Mounting
(maximum panel thickness: 3mm)
- Remove cover T from the equipment (Fig.1a or Fig.1b).
- Open the equipment and separate the front part of the housing (Fig.2).
- Replace the joint installed at the front by the panelling joint, ensuring that it is in the right
position.
- Make an opening in the panel with the dimensions indicated (Fig.4a or Fig.4b).
- Drill the holes for the glands that are necessary for the cables to pass through, guided by
the pre-cut centres on the sides of the housing.
- Finish drilling holes G, H, J with a 4 mm bit (Fig.3a or Fig.3b).
- Anchor the glands to the equipment.
- Insert the cables into the glands.
- Join the front with the housing, through the panel and tighten the 45 mm screws through
holes D, E, F, G H, J (Fig.3a or Fig.3b).
- After connecting the cables in accordance with the connection diagram, close cover T, and
insert and tighten screws A, B, C (Fig.1a or Fig.1b).
FIG.1a
222,1 mm
140 mm
FIG.3a
214 mm
PANEL CUT-OUT
FIG.4a
3.3- Lamp Mounting
(on equipment that has an alarm indicating a person is trapped inside)
- See AKO-52064 instructions
- 1 -
FIG.1b
337,6 mm
255,5 mm
FIG.3b
330 mm
PANEL CUT-OUT
FIG.4b
FIG.2