Placing the appliance

− Take the installation requirements into account (see chapter3)
− Place the appliance into the proper position and if necessary, adjust the height with the
adjustable legs.
− Adjusting the height and leveling the hearth with a spirit level.(see fig. 1.5)
− Always place the appliance with a minimum distance of 1000[mm] from combustible materials or
objects.
− Place the discharge pipes in such a way that situations with a risk of fire can never occur.
− Always place the appliance in front of a wall of non-combustible and heat-resistant material.
− Always maintain a minimum distance between appliance and a back wall.
− Take sufficient measure to prevent temperature of a wall behind the chimney breast becoming
too high, including the materials and/or objects behind it.
− Do not cover the appliance or wrap it in an insulation blanket of any other material.
− Make sure that the appliance is installed in a stable position.

Mounting the smoke emission outlet materials

− In case of a wall or roof terminal, the hole must be at least 5 mm bigger than the diameter of the
flue material.
− Horizontal parts must be installed at a (3 degree) slope up away the appliance.
− Build up the system from the appliance. If this is not possible, you should make use of a
adjustable pipe.
− For fitting the system a ½ metre cut-down pipe should be used. Make sure the inner pipe is
always 2 cm longer than the outer pipe. Wall and roof terminal are also shortened. These parts
must be secured with self-tapping screws.
− Do not insulate but ventilate build-in flue material (approx.100cm2)

Building a false chimney breast

− Before constructing the false chimney breast we advise you to perform a function test with the
gas hearth as described in chapter 7 "checking the installation"
− Construct false chimney to comply with the installation requirements.

Chimney breast

− Construct the false chimney breast from non- combustible sheet metal in combination with metal
profiles or of brickwork / aerated concrete bricks.
− Take the grates and the service panel (see fig. 1.1 and1.2 )into account. Place a protective shield
made of non- combustible material above the grates (see fig.1.1A) .
− Always use a lintel if the chimney breast is constructed of brickwork. These should not be placed
directly onto the appliance.

Frameless

− Construct the chimney breast against the build-in frame (see fig. 1.1B).
− Keep a minimum margin of 3 mm between chimney breast and the appliance in connection with
the expansion of the appliance.
− The depth of the recess has no influence on the removal of the glass.