Cylon CBT-STAT 사용자 설명서 - 페이지 13

{카테고리_이름} Cylon CBT-STAT에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. Cylon CBT-STAT 20 페이지.

Cylon CBT-STAT 사용자 설명서

USING THE ENGINEERING MODE MENUS

When the correct password is entered, the Engineering Menu page
in the display as follows:
st
The 1
line (large digits)
Available parameters on page 14).
nd
The 2
line (small digits)
Navigating through the Engineering Menus
To scroll through the lines on the current page, use the the up
To navigate to a different page, use the right
Editing a parameter
To view or edit the value of the parameter on the current line, press and hold ("long-press") the right button
The 2nd line (small digits)
most character (when the value is a number) or the whole text (when the value is an option label) flashing.
Press the up button
Note:
In the case of digits, this is not a simple change to the digit itself, but an addition or subtraction
(from the full parameter value) of the value represented by that specific digit.
For example, if the value is +127, then the left-most digit ("1") represents 100. If that digit is
selected, then the down
another press of the Down button will change it to -073 (subtract 100 from 27).
Use the left and right buttons to move between digits
To reset the parameter to its default value, press and hold the left button
To apply the edited value, press and hold the right button
MAN0120US rev 16


shows the Page number and Line number of the commissioning parameters (see
a
shows the label for the parameter addressed by the current line.
b
and left
b
will change to show the current value for that parameter, with either the right-
or down button
to change the value of the flashing digit or label.
button will first change it to +027 (subtract 100 from 127), then
© Cylon Controls Ltd.

line
will be displayed. This is indicated
and down
buttons (short press).
buttons (short press).
.