A4 INTRINSICALLY SAFE &
NON-INCENDIVE RATED PRESSURE
TRANSMITTER INSTRUCTION SHEET
INSTALLATION NOTES≥
Voc OR Vt ≤30VDC
Isc OR It ≤100mA
Ca≥ 0.053uF + Ccable
La ≥ 0.364uH + Lcable
1. THE INTRINSIC SAFETY ENTITY CONCEPT ALLOWS THE INTERCONNECTION
OF TWO INTRINSICALLY SAFE DEVICES FM APPROVED WITH ENTITY
PARAMETERS NOT SPECIFICALLY EXAMINED IN COMBINATION AS A
SYSTEM WHEN: Uo OR Voc OR V≤t Vmax, Io OR Isc OR≤ It Imax, Ca OR Co
≥ Ci + Ccable, La OR ≥Lo Li +Lcable≤, Po Pi.
2. THE NONINCENDIVE FIELD WIRING CONCEPT ALLOWS INTERCONNECTION
OF NONINCENDING FIELD WIRING APPARATUS WITH ASSOCIATED
NONINCENDIVE FIELD APPARATUS USING ANY OF THE WIRING METHODS
PERMITTED FOR NON3HAZARDOUS (UNCLASSIFIED) LOCATIONS WHEN: Uo
OR Voc OR Vt Vmax, Io OR Isc OR It Imax, Ca OR Co + Ccable, La OR Lo Li
+Lcable, Po Pi.
3. FOR DIVISION 1 INSTALLATIONS, THE CONFIGURATION OF ASSOCIATED
APPARATUS SHALL BE FM APPROVED UNDER ENTITY CONCEPT.
HAZARDOUS (CLASSIFIED) AREA
4. FOR DIVISION 2 INSTALLATIONS USING NONINCENDIVE FIELD WIRING
CONCEPTS THE ASSOCIATED APPARATUS SHALL BE FM APPROVED UNDER
THE ENTITY
CONCEPT OR NONINCENDIVE FIELD WIRING CONCEPT.
HAZARDOUS (CLASSIFIED) AREA
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
MODEL A2X & A4 SERIES
4-20MA TRANSMITTER
©2018 Ashcroft Inc., 250 East Main Street, Stratford, CT 06614-5145, USA, Tel: 203-378-8281, Fax: 203-385-0499, www.ashcroft.com
All sales subject to standard terms and conditions of sale. A4_transducer_im_ RevB_(009-10166)_09-18
4.3 FM INSTALLATION GUIDELINES
INSTALLATION FOR FM
INTRINSICALLY SAFE CLASS 1, GROUPS A, B, C & D &
CLASS ll, GROUPS E, F & G &
CLASS I, DIVISION 1 & 2,
GROUPS A, B, C, & D;
CLASS II, DIVISION 1 & 2,
GROUPS E, F & G, CLASS III
CLASS I, DIVISION 1 & 2,
GROUPS A, B, C, & D;
CLASS II, DIVISION 1 & 2,
GROUPS E, F & G, CLASS III
CLASS lll
5. FOR DIVISION 2 INSTALLATIONS THE ASSOCIATED APPARATUS IS
NOT REQUIRED TO BE FM APPROVED UNDER ENTITY CONCEPT OR
NONINCENDIVE FIELD WIRING CONCEPT IF THE
A2X(4-20mA) & A4 SERIES PRESSURE TRANSDUCER IS INSTALLED IN
ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE (ANSI/NFPA 70)
FOR DIVISION 2 WIRING METHODS EXCLUDING NONINCENDIVE FIELD
WIRING.
6. CONTROL EQUIPMENT CONNECTED TO THE ASSOCIATED APPARATUS
SHALL NOT USE OR GENERATE MORE THAN 250VRMS OR VDC.
7. DIVISION 1 INSTALLATIONS SHOULD BE IN ACCORDANCE WITH ANSI/
ISA RP12.06.01, ``INSTALLATION OF INTRINSICALLY SAFE SYSTEMS FOR
HAZARDOUS (CLASSIFIED) LOCATIONS'' AND THE NATIONAL ELECTRICAL
CODE (ANSI/NFPA 70).
8. ASSOCIATED APPARATUS MANUFACTURERS INSTALLATION DRAWING
SHALL BE FOLLOWED WHEN INSTALLING THIS EQUIPMENT.
9. RUN SHIELDED INTERCONNECTION CABLE WITH SHIELD CONNECTED TO
FM APPROVED ASSOCIATED APPARATUS GROUND.
10. WARNING – DO NOT OPEN WHEN ENERGIZED.
NON-HAZARDOUS
11. WARNING – DO NOT DISCONNECT EQUIPMENT UNLESS AREA IS KNOWN
(UNCLASSIFIED) AREA
TO BE NON-HAZARDOUS.
NON-HAZARDOUS
(UNCLASSIFIED) AREA
V+
BARRIER
V–
R LOAD
250 OHM
TYP.
V+
BARRIER
V–
R LOAD
250 OHM
TYP.
V+
BARRIER
V–
R LOAD
250 OHM
TYP.
V+
BARRIER
V–
R LOAD
250 OHM
INSTALLATION NOTES:
Voc OR Vt ≤30VDC
Isc OR It ≤100mA
Ca≥ 0.053uF + Ccable
La ≥ 0.364uH + Lcable
1. THE INTRINSIC SAFETY ENT
SICALLY SAFE DEVICES FM
EXAMINED IN COMBINATIO
INSTALLATION NOTES:
It Imax, Ca OR Co ≥ Ci + Cc
Voc OR Vt ≤30VDC
Isc OR It ≤100mA
2. THE NONINCENDIVE FIELD
Ca≥ 0.053uF + Ccable
ING FIELD WIRING APPARA
La ≥ 0.364uH + Lcable
+24 VDC TYP.
USING ANY OF THE WIRING
LOCATIONS WHEN: Uo OR
1. THE INTRINSIC SAFETY EN
+
Lo Li +Lcable, Po Pi.
SICALLY SAFE DEVICES FM
V OUT
EXAMINED IN COMBINATIO
3. FOR DIVISION 1 INSTALLAT
It Imax, Ca OR Co ≥ Ci + Cc
(1-5 V TYP.)
BE FM APPROVED UNDER
2. THE NONINCENDIVE FIELD
4. FOR DIVISION 2 INSTALLA
ING FIELD WIRING APPAR
+24 VDC TYP.
ASSOCIATED APPARATUS
USING ANY OF THE WIRIN
NONINCENDIVE FIELD WIR
LOCATIONS WHEN: Uo OR
+
Lo Li +Lcable, Po Pi.
5. FOR DIVISION 2 INSTALLAT
V OUT
APPROVED UNDER ENTITY
3. FOR DIVISION 1 INSTALLA
(1-5 V TYP.)
A2 SERIES PRESSURE TRA
BE FM APPROVED UNDER
ELECTRICAL CODE (ANSI/N
–24 VDC TYP.
NONINCENDIVE FIELD WIR
4. FOR DIVISION 2 INSTALLA
ASSOCIATED APPARATUS
6. CONTROL EQUIPMENT CO
NONINCENDIVE FIELD WIR
GENERATE MORE THAN 25
V OUT
5. FOR DIVISION 2 INSTALLAT
(1-5 V TYP.)
7. DIVISION 1 INSTALLATION
APPROVED UNDER ENTITY
"INSTALLATION OF INTRIN
A2 SERIES PRESSURE TRA
LOCATIONS" AND THE NAT
ELECTRICAL CODE (ANSI/N
–24 VDC TYP.
NONINCENDIVE FIELD WIR
8. ASSOCIATED APPARATUS M
WHEN INSTALLING THIS EQ
6. CONTROL EQUIPMENT CO
GENERATE MORE THAN 2
V OUT
9. RUN SHIELDED INTERCON
ASSOCIATED APPARATUS
(1-5 V TYP.)
7. DIVISION 1 INSTALLATION
INTRINSICAL
C
INTRINSICAL