Ashcroft GC30 빠른 시작 매뉴얼 - 페이지 5

{카테고리_이름} Ashcroft GC30에 대한 빠른 시작 매뉴얼을 온라인으로 검색하거나 PDF를 다운로드하세요. Ashcroft GC30 7 페이지. Ultra-compact digital differential pressure transducer
Ashcroft GC30에 대해서도 마찬가지입니다: 설치 및 유지보수 지침 매뉴얼 (20 페이지)

Ashcroft GC30 빠른 시작 매뉴얼
Product Information Page
OF1 To delay output 1switch turn off.
Step
Delay output 1 switch turn off shall not be used for this application.
4
Press Up or Down arrow until 0.00 is displayed.
Press and release MODE button to select and move to the next step.
A-2 To enter output 2 switch shutdown set point .750 IWC.
Press UP or Down until .750 is displayed.
Step
Press and release MODE button to select and move to the next step.
5
b-1 To enter output 2 switch dead band.
Step
Set dead band to .550 IWC to deactivate switch at .200 IWC.
6
Press UP or Down until .550 is displayed.
Press and release MODE button to select and move to the next step.
On2 To delay output 2 switch turn on.
Step
Delay output 2 switch turn on shall not be used for this application.
7
Press Up or Down arrow until 0.00 is displayed.
Press and release M button to select and move to the next step.
OF2 To delay output 2 switch turn off.
Step
Delay output 2 switch turn off shall not be used for this application.
8
Press Up or Down arrow until 0.00 is displayed.
Press and release MODE button to select and move to the next step.
LoP Loop check mode allows program and switches verification with
the transmitter pressurized or non-pressurized. It simulates the
process and allows for troubleshooting.
Step
Press Up or Down arrow to simulate pressure values.
9
After verification press and hold MODE button for more than three
seconds to return to measuring mode.
All specifications are subject to change without notice.
All sales subject to standard terms and conditions.
© 2017 Ashcroft Inc.
ashcroft.com
info@ ashcroft.com
1.800.328.8258
Rev. A 02/17, Page 5 of 7