Function
Behaviour with internal device faults
If internal device faults were detected during the test function, the display
backlight changes into red and an error messages (failure code: „Int.1")
is indicated. The indicator relays K1 and K2 switch to the alarm state.
Behavior on faulty connection
When detecting broken wire on terminals L(+)/L(-), the measurement is
disabled. The reaction time could be up to 2 min. The monitoring relays
K1 and K2 go in alarm state, the backlight changes to red. The display
shows the fault message „L+/L-". After removing the interruption the fault is
automatically reset (max. reaction time up to 2 min) and the measurement
of the insulation resistance is continued.
Stored alarm values remain stored. An interruption of the protective
earth connections PE1/PE2 causes the same reaction as interrupting the
measuring circuit, only the display shows „PE1-PE2".
External control input
To terminals X1/X2 an external combined Test-/Reset button can be
connected. If the terminals X1/X2 are bridged for approx.. 1 s the test mode
is started. This has the same function as pressing the internal test button.
When bridging X1/X2 for > 3 s, a stored alarm will be reset. This has the
same function as pressing the internal reset button.
Programming/setting of parameters/set-up of the insulation monitor
The response values for alarm and pre-alarm can be adjusted via 2 rotary
switches „R
" and „R
" on the front of the device. New setting are immediately
A
pA
active and do not require a restart of the unit. More settings can be done
with the 3 buttons and the display menu in programming mode. To start the
programming mode, the button „Set/ESC" has to be pressed for approx.
2 s. To avoid unauthorized manipulation, this button as well as the rotary
switches „R
" and „R
" are located behind a sealable transparent cover. When
A
pA
the device changes to programming mode, the measurement is stopped,
the display back light changes to orange color and the first parameter is
displayed. To scroll the different parameters, the button „Set/ESC" has to
be pressed short. With the 2 scroll buttons (Scroll-Up „" and Scroll-Down
„") the settings can be modified.
The first parameter is the broken wire detection in the measuring circuit
„BrWiD". Possible setting are continuously on („on"), continuously off („oFF")
or only active during self-test. The default is „on".
The second parameter is alarm memory „Mem.". Here are 2 options available
manual reset („on") und auto reset („oFF"). The default value is „oFF".
The third parameter is the relay operation principle „Rel." Settings are:
de-energized on trip („n.c.") and energized on trip („n.o."). The default
value is „n.c.".
The fourth parameter is the type of network connection „Net". Selection
are AC Network(„Ac"),DC-Network („dc") or 3NAC-Network („3nAc"). The
default value is „Ac".
The fifth parameter ist the setting oft the maximum leakage capacity
(„CE[µF]"). This can be adjusted to 30 µF ("30"), 100 µF ("100") and
300 µF ("300"). The default value is „30".
The leave the programming mode the button „Set/ESC" has to be pressed
for 2 s. The settings will be activated and stored permanently. After that the
device makes a restart similar to power on.
Default-Setting of Parameters
Nr.
Parameter
Broken wire detect in measuring circuit
1
"Broken Wire Detect"
Storing insulation fault message
2
"Memory"
Switching mode of output relays
3
"Relay"
Power supply type
4
"Net"
Max. line capacitance
5
"CE[µF]"
Circuit Diagram
L(+)
L(-)
A1(+)
L(+) L(-)
11
U H
PE1
PE2
12
X1 X2
11 12 14 21 22 24
PE1
Connection Terminals
Terminal designation
Signal description
A1(+), A2
Auxiliarx voltage AC or DC
L(+), L(-)
Connection for measuring ciruit
PE1, PE2
Connection for protective conductor
Control input (combined external
X1, X2
Test- and Reset-input)
11, 12, 13
Alarm signal relay K1(1 changeover contact)
Prewarning signal relay K2 (1 changeover
21, 22, 23
contact)
3
Default-Set
on
off
n.c. (normally closed)
de-energized on trip
AC
30
A2
21
14
22
24
PE2
M11453_b