7.2
Product Error Codes
7.2.1
WPT
Code
Cause
Indicates that the WPT is
performing a discovery
dy
operation and it should not
be disturbed.
Indicates that the WPT is
dt
performing a diagnostic
operation.
Indicates that the WPT is
Fd
performing a forced
discovery operation.
Indicates that the buttons
UL
are unlocked by the user.
Indicates that the buttons
LC
are locked.
Discovery error – Not able
E0
to connect to nearest
repeater or HUSB
Time synchronization error
– Not able to synchronize
E1
the WPT time with the
wireless network
Radio error – Not able to
E2
send/receive data
Optical Sensor Error – Not
E4
able to properly position
motor/cam
WPT Operations and Maintenance
Document No. 910-00028-01, Rev 1
Possible Solution
This indication disappears automatically
after a few seconds.
This indication disappears automatically
after a few seconds.
This indication disappears automatically
after a few seconds.
This indication disappears automatically
after a few seconds.
This indication disappears automatically
after a few seconds.
Retry discovery by pressing any button.
Check if repeater or HUSB is working.
Try resetting the repeater.
Try with a different position of the
repeater/ HUSB if feasible.
If this error occurs after successful
commissioning of the system, the WPT
will recover from this error within a couple
of refresh cycles.
Restart the unit with removing and
inserting the battery. If the error
continues, the device requires
replacement. Contact the distributor.
This error is an indication of a defective
device. The unit should be replaced.
Page 8 of 10