EG4 EG4-LL 사용자 설명서 - 페이지 9

{카테고리_이름} EG4 EG4-LL에 대한 사용자 설명서을 온라인으로 검색하거나 PDF를 다운로드하세요. EG4 EG4-LL 20 페이지. Rack mounted 48v 100ah/24v 200ah

EG4 EG4-LL 사용자 설명서
In the above figure, there are 6 EG4-LL 48V 100Ah batteries wired in parallel. This battery bank still
maintains the appropriate 48V needed for most Inverter/Charger systems. However, the Amp hour rating
of this bank has increased to 600Ah.
WARNING: Do NOT parallel batteries by using jumper wires on the double terminals. This will
cause high amperage in the final jumpers and potentially excessive amperage on the battery
terminals.
WARNING: When adding or removing a battery from the rack/cabinet,
turn off ALL batteries and remove all cables from the batteries. This
will ensure that you do not accidentally make contact with live
(powered) busbars. This can cause serious injury and/or death.
Connecting Your Batteries to a Busbar
EG4 recommends that you only use a properly sized (amp rated) busbar to parallel batteries together.
1. Connect the battery cables to your positive busbar by removing the bus bolts, inserting them
through the eyelets of the proper cable, and reseating the bolt into the busbar to 60 in-lbs/7nm.
Repeat with all positive cables.
2. Connect the battery cables to your negative busbar by removing the bus bolts, inserting them
through the eyelets of the proper cable, and reseating the bolt into the busbar to the correct
torque. Repeat with all negative cables.
Battery Charging
Once you are ready to charge your batteries, you must ensure that you use the proper settings. This will
ensure that you don't over-charge or damage your batteries.
1. Bulk/Absorption: 55.5V (+/- 2%)
2. Float: 54V (+/- 2%)
3. Battery Charge Temperature Range: 32°F - 113°F
4. Battery Discharge Temperature Range: -4°F - 131°F
5. Cell Charge Temperature Range: >32°F or <158°F
6. Cell Discharge Temperature Range: >32°F or <158°F
8