Ambi-Rad UF Series 2 사용자 지침 - 페이지 2

{카테고리_이름} Ambi-Rad UF Series 2에 대한 사용자 지침을 온라인으로 검색하거나 PDF를 다운로드하세요. Ambi-Rad UF Series 2 2 페이지. Gas-fired unit heaters uf series 2;

Figure 2B - Size UF400 Multifunctional Control
Valve (NOTE: Size UF400 may be fitted with this
valve or the valve illustrated in Figure 2A.)
Stop
Start
Button
Button
Pilot Regulating
Screw
TO SHUT DOWN THE HEATER FOR
SHORT PERIOD:
Adjust the room temperature controller to its lowest
setting or "OFF". The fan will continue to run for a
short period to cool the heat exchanger. The pilot will
remain alight.
WARNING: The electrical isolator
should only be used in an emergency and
should not be used for closing down the
main burner, as it switches off the fan pre-
maturely and may damage the heat ex-
changer, invalidating the warranty.
Figure 3 - CLEARANCES REQUIRED
Sales & Service by:
Ambi-Rad Limited,
Fens Pool Avenue,
Wallows Industrial Estate,
Brierley Hill,
West Midlands DY5 1QA
Telephone: 01384 489 700
Fax: 01384 489 707
WA005 Page 2
Pressure Regulator
Cover Screw
Outlet Pressure
Test Port
TO SHUT DOWN THE HEATER FOR
EXTENDED PERIOD:
1) Adjust the room temperature controller to its lowest setting
or "OFF".
2)
Valve in Figure 2A - Rotate the knob on the multifunctional valve
(approximately 1/12 of a full rotation).
in a clockwise direction
Valve in Figure 2B - Push in and release the red stop button
(marked O) on the valve.
3) After the fan has stopped, turn "OFF" the gas supply and
the electrical supply.
NORMAL OPERATING SEQUENCE (pilot
lighted):
1) Room thermostat senses need for heat.
2) Main gas valve in the multifunctional control valve is
energised.
3) Main burners are ignited by permanent pilot light.
4) In approximately 45 seconds, the fan control switch senses
heat exchanger temperature and turns on the fan.
5) Room temperature control senses sufficient heat.
6) Main gas valve is de-energised, and main burners are extin-
guished.
7) After approximately 120 seconds, the fan control switch
turns off the fan.

MAINTENANCE AND SERVICE:

To ensure safe and efficient operation, this heater should be
serviced at least annually. It is strongly recommended that the
installing heating engineer or AMBI-RAD Service Division be
contacted to provide the necessary service. Retain on file a
copy of the service instructions for this heater.
© 2000 Thomas & Betts Corporation, All rights reserved.
Allow Front Clearance as
follows:
Models
mm
in.
25-125
1830
72
165-250
2440
96
300-400
3050
120
0600 500 YL8998