STOPPING YOUR GENERATOR
1. Disconnect the load from the generator.
2. Turn off the air switch of the generator.
3. Set the speed lever at "RUN" position, and run the generator without the load for
3 minutes. Do not stop the engine suddenly, otherwise the temperature will
increase abnormally, the nozzle will be blocked and the generator will be
damaged.
4. Press down the stop lever.
5. Turn the electric starter key to "OFF".
6. Turn the fuel cock lever to the "S" position.
7. Pull out the recoil starter handle until you feel resistance (at this position, both
the intake/exhaust valves are closed) and leave the handle in this position. This
prevents the engine from rusting.
WARNING
If the engine keeps on running even after the speed lever is placed at the "STOP"
position, either turn the fuel cock to the "CLOSE" position or loosen the nut of the high
pressure fuel pipe on the side of the pump to stop the engine.
Do not stop the engine with the decompression lever.
Do not stop the generation set with load. Stop it after the load is removed
13