Exert loads with the specified parameters. Do not start two or more machines
simultaneously. Start them one by one. Do not use floodlights with other machines.
AC application
1. Make sure to run the generator at the suggested speed.
2. After switching on the air switch, observe the voltmeter on the panel of the
control cabinet; it should point to 230V + 5%(50Hz) for the single-phase
generating set; 400V + 5%(50Hz) for the three-phase generating set, then the
loading can be carried out.
3. When the double voltage generator changes over the voltage, the air switch
should be set at the "OFF" position. Otherwise the generator and the electrical
devices will be burned out and damaged.
4. Connect the equipment to the generator in order. The heavy-duty motor should
be connected first, then the light-duty motors. If the operation is false, the
generator will lag or stop suddenly. It is necessary to unload the generating set
immediately and turn off the main switch and do checks.
5. For the three-phase generator: Balance three phases during the operation. Stop
the engine to check if the tolerance exceeds 20%. Be sure to keep the tolerance
among the three phases less than 20%. The load for each phase must be below
the rated load as will as the current must be less than rated current. A, B, C, D
(or U, V, W, N) phase arrangement should be from left to right, or clockwise.
6. When connecting devices to the generator, make sure to connect these devices
in order: Connect the large loads onto the generator first. If everything is
functional, smaller loads can then be added. If the generator shuts off, it may be
because the load being drawn by all the various devices are too high. In this
event, decrease the number of small devices until everything is functional. The
total drawn power should not exceed the maximum output power of the
generator. In order to reset the generator after overdrawn power, let it sit for
several minutes. If the indication of the voltmeter is too high or too low, adjust the
speed accordingly. If there are problems, stop the generator immediately and fix
the issue.