■Example of mixed installation with 2-wire (non-isolated) and
4-wire (isolated) terminals
Red:
Red: DP
DP
AnyWireASLINK
master
Black:
Black: DN
DN
ASLINK
General-purpose
lter
power supply lter
Red: DP
*
24V DC
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Red: DP
Black: DN
Green: 24V
White: 0V
Dedicated at cable
1.25mm
2
(4-wire)
4P link connector is
convenient for
branching.
The sum of the
portions of DP, DN is
the total line length.
*
Black: DN
Red: DP
24V DC
AnyWireASLINK terminator
One terminator should be connected to the DP, DN
terminal farthest from the AnyWireASLINK master unit.
Connect it correctly so as not to set the wrong polarity.
To connect loads (e.g. I/O ports) that are
CAUTION
controlled with a power supply other than the
one used for the AnyWireASLINK system,
always use a 4-wire (isolated) terminal.
Otherwise, malfunction may be caused.
2 points
2 points
8 points
Red: DP
Black: DN
1 point
1 point
4 points
Red: DP
Black: DN
16 points
8 points
Black: DN
The branching
2 points
has no limitation.
Red: DP
2 points
Red: DP
[Notes on Combined Use of 4-Wire (Isolated) Terminal]
If the total length of the sections where all the DP, DN, 24V, and 0V lines
run in parallel in the power supply system is more than 50m, connect
an ASLINK lter (Type ANF-01) or a lter manufactured by COSEL Co.,
Ltd. (Type EAC-06-472) in series to the 24V and 0V lines at a position
where these four lines start running in parallel.
This will improve noise resistance, suppress the adverse effects of
crosstalk caused by transmitted signals, and stabilize signals.
The above
supplied to all terminals collectively from the power supply for the
master or power is supplied to each terminal individually from their local
power supply.
Insert the "ASLINK lter [Type ANF-01]" regardless of installation
method and distance when complying with CE Standard.
■Filter allowable current
Product
ASLINK lter
Filter of COSEL Co., Ltd. EAC-06-472 MAX 6A/24V DC
■AnyWire Type: ANF-01 Connection example
① Power supply to the entire system
AnyWireASLINK master
General-purpose power
supply lter
(Use it if necessary.)
24V DC stabilized
power supply
If the total length of the section
where all the DP, DN, 24V, and 0V
lines run in parallel is more than 50m
Black: DN
2 points
-L*D*1AW 4/14-
lters must be inserted regardless of whether power is
Type
ANF-01
DP
DN
24V
0V
LG
POWER IN
ANF-01
0V
24V
SLAVE
L N FG
~
Allowable power current
MAX 5A/24V DC
PE
0V
24V
0V
24V
2-wire
DP
terminal
DN
DP
4-wire
DN
24V
terminal
0V
Terminator