AMC 2751 Instruction Manual - Page 10

Browse online or download pdf Instruction Manual for Transmitter AMC 2751. AMC 2751 16 pages. Transmitter with electrochemical sensor

4.2 CABLE SELECTION AND WIRING

To pass the 4 to 20mA signal from the AMC-2751 sensor/transmitter to the monitor, a two conductor,
shielded cable is recommended. Note that the same wire pair can be used for both signal and power due
to the low power current loop design of the AMC-2751. For best signal transmission and maximum noise
rejection, it is recommended to run the cable through steel conduit ( the cable must be grounded at the
monitor or power supply).
The AMC-2751 minimum stated voltage requirement of 12 VDC is based on the use of a 250 ohm load
resistor to covert the current signal into a voltage signal. The maximum Cable Distance Chart (Figure 3)
assumes the use of a 250 ohm load resistor, and a safety margin of .5 VDC. It gives absolute maximum
cable lengths for a range of wire gauges. Note that the user must take responsibility for the selection of
wire gage, power supply voltage and load resistor used as the values shown may not be suitable for all
applications.
WIRE GAUGE
R/1000 ft
MAXIMUM
@12VDC
DISTANCE IN
FEET
@24VDC
(METERS)
FIGURE 3: Cable Selection Chart

4.2.1 SENSOR/TRANSMITTER TO MONITOR WIRING

The AMC-2751 sensor/transmitter should be connected to the monitor, as shown in Figure 4, by
a twisted pair cable for the conduction of the 4 to 20 mA signal.
See the following connections going from the AMC-2751 to the monitor for each channel:
AMC-2751 Terminal (+) -------- goes to------- Monitor Channel Terminal (+)
AMC-2751 Terminal (-) -------- goes to------- Monitor Channel Terminal (SIG)
AMC-2751 Transmitter & Sensor
AWG
22
16.2 ohms
400
(120)
10000
(3000)
(Based on 250 Ohm Load Resistor & V
20
10.3 ohms
6.5 ohms
700
1000
(210)
(300)
16000
Over 20000
(4800)
(6000)
8
18
16
4.3 ohms
1500
(4500)
Over 20000
(6000)
= .5 V)
SM