Dontek AQUASMART 5 SV Instruction Manual - Page 2
Browse online or download pdf Instruction Manual for Controller Dontek AQUASMART 5 SV. Dontek AQUASMART 5 SV 13 pages.
INSTALLATION INSTRUCTIONS
THIS APPLIANCE IS NOT INTENDED FOR USE BY YOUNG CHILDREN OR INFIRM PERSONS WITHOUT
SUPERVISION. PLEASE ENSURE THAT YOUNG CHILDREN ARE SUPERVISED TO ENSURE THAT THEY DO NOT
PLAY WITH THE APPLIANCE.
Ideally, as with all pool equipment, the controller should be installed out of direct weather.
Find a suitable location to mount the control box.
The controller should be no closer than 3 metres from the water's edge and a
minimum 600mm above ground. The power cable is 1.8m long and should be plugged
CONTROLLER
directly into a general power outlet, not into an extension lead.
MOUNTING
Fix the mounting bracket to a solid structure with the screw and wall plug kit provided.
Slide the controller on, locking it into place. Adjust the screws on the back of unit to
ensure a snug fit.
To remove unit, lift and gently pull away from structure.
The Circulation pump plugs into the 240V socket labelled PUMP.
PUMP
IF a solar booster pump is being used, it will plug into the 240V socket labelled as
SOLAR or AUX.
CONNECTION
The maximum load is 9.98 AMPS at 2395W.
Set the heaters temperature limit to maximum (40°C). The heaters internal control will
be interrupted, to turn off heating. The heater interlock cable connects to the green
socket marked INT which switches on (closes) the voltage free NO/C relay contacts
when the heater is to be turned on. The heater end of the interlock cable connects in
series with the heater's pressure/flow or fireman's switch. Contact the heater
manufacturer for the best location to connect to.
The heater interlock is for extra low-voltage (MAX 24V at 1Amp) switching only. If the
heater's control circuit is 240Vac, an external relay KIT can be purchased separately
and is to be connected by a licensed electrician.
HEATER
For Internal connection to pool heater (check with heater manufacturer).
CONTROL
Illustration of a typical installation to the heaters pressure or flow switch.
A valve actuator is used to divert water flow to the solar collector in the retro-fit
plumbing configuration. Connect the valve actuator to the green socket marked VALVE.
If wiring your own supplied valve then wire as per the label on the bottom of the
controller (Red, Black then White). Red and white are for direction control and black is
VALVE
the common. Ensure the switch on the valve actuator is in an ON position. Refer to the
valve actuator instructions for mounting requirements cam adjustments.
Maximum power for the VALVE output is 24VAC.
AQUASMART 5 SV v1.4
2