Amerisolar AS-6P Installation Manual - Page 8
Browse online or download pdf Installation Manual for Solar panel Amerisolar AS-6P. Amerisolar AS-6P 11 pages. Solar module
Worldwide Energy and Manufacturing (Nantong) Co., Limited
The maximum voltage supported on an installation (Vmax. System), with Amerisolar's
photovoltaic modules, is presented in the following table:
IEC
Maximum System Voltage (V)
1000
6.2 Grouding
Grouding modules is necessary to reduce or eliminate shock and fire hazards. All module
frames and mounting racks must be properly grounded in accordance with local and national
electrical codes. Proper grounding is achieved by connecting the module frames and
mounting racks continuously using a suitable grounding conductor. The grounding conductor
or strap may be copper, copper alloy, or other material acceptable for use as an electrical
conductor.
(a) Grounding by using grounded clamp
There are two grounding holes with 4.0 mm diameter in the middle of the long frames of the
modules. The grounding between modules must be approved by qualified electrician. And the
grounding device must be produced by qualified electrical manufacture. The recommended
twist torque value is 2.3 N.m. A copper core in size of 12 AWG can be used as grounding
clamp. The copper wire should not be compressed during the installation.
Note: The figure above is using TYCO. 1954381-1 (recommended)
Fig.5 Grounding method (a)
6