DAB PUMPS ACTIVE DRIVER M/M 1.1 Instruction For Installation And Maintenance - Page 12

Browse online or download pdf Instruction For Installation And Maintenance for Control Systems DAB PUMPS ACTIVE DRIVER M/M 1.1. DAB PUMPS ACTIVE DRIVER M/M 1.1 16 pages.

8.5.11 O1: Setting output 1 function ( "active alarm" ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
O2: Setting output 2 function ( "pump operating ) (excluding A.D. M/M 1.1 and A.D. M/T 1.0)
Assigning the parameters that associate functions with the digital outputs OUT1; OUT2
Assigning the
parameters
Each function is disabled.
o1
Contact always open
Each function is disabled.
o2
Contact always open
9.
DISPLAYS ( see table no. 14 page 36 )
9.1
DISPLAYS OF THE MAIN VALUES
Access key MODE
From normal operating status, pressing the MODE key displays the following values:
Fr: Display of the current rotation frequency (in Hz).
UP: Display of pressure (in bar).
C1: Display of the phase current of the electropump (in A).
(excluding A.D. M/M 1.1 and A.D. M/T 1.0)
UE: Display of the version of the software with which the appliance is equipped.
9.2

MONITOR DISPLAYS

Access keys SET & - for 2 seconds
From normal operating status, pressing the key SET & - enters the MONITOR function where the
following values are displayed:
( NB: to scroll through the values press the MODE key)
UF: Display of the flow
Display of the instantaneous flow.
Parameter to be used only as a reference in programming.
ZF: Display of zero flow
Display of the reading of the flow sensor on which zero was acquired (with electropump switched off).
During normal operation the ACTIVE DRIVER will use this parameter to switch off the electropump.
FM: Display of the maximum rotation frequency (in Hz)
tE: Display of the temperature of the power stages (in °C)
GS: Display of running status
SP = pump operating to maintain pressure "SP".
P1 = pump operating to maintain pressure "P1" (input 2 active).
AG = pump operating for "anti-frost".
FF: Display of fault history (+ & - to scroll through the alarms)
There is a queue of 16 positions for containing the last 16 faults which have occurred during system
operation. By pressing the – key you can go back in history and stop at the oldest fault present, whereas
by pressing the + key you can go forward in history and stop at the most recent fault present.
The decimal point identifies the last fault to have occurred in chronological order.
The history contains at the most 16 positions. Each new fault is inserted in the most recent position
(decimal point). For each fault after the sixteenth, the oldest one in the queue is erased. The history of
the faults is never erased but only updated as new faults occur. Manual reset and switching off of the
appliance do not erase the history of faults.
10.
ACCESS
TO MANUAL MODE OF THE MACHINE
Access keys SET & + & - for 5 seconds
During this phase all the controls and protection systems of the ACTIVE DRIVER are
disabled!
ENGLISH
0
Each function is disabled.
Contact always closed
Each function is disabled.
Contact always closed
Value
1
In case of blocking errors
the contact closes (default)
When the electropump is
operating the contact closes
(default)
33
2
In case of blocking errors
the contact opens
When the electropump is
operating the contact
opens
3