Ametek Magnetrol SOLITEL Installation And Operating Manual - Page 6
Browse online or download pdf Installation And Operating Manual for Switch Ametek Magnetrol SOLITEL. Ametek Magnetrol SOLITEL 13 pages.
Power
Material Level
On
High
On
Low
Fail
High/Low
6
Fail-Safe Jumper
LED Color
position
Green
B position
Red
position
Red
B position
Green
/B
2.5
Calibration
Ensure that the fail-safe jumper is installed in the proper
position as described in Table 1. The LED will show
red when in alarm condition and green when in normal
condition. Test the operation of the switch by holding,
and then releasing the vibrating rod; the LED will
change color.
The sensitivity of the switch can be changed using the
density adjustment screw. Note that this adjustment screw
has 270 degrees of rotation. Do not rotate past the stops.
NOTE: If the adjustment is too sensitive, the switch may detect
even slight residue of material rather than level.
Prior to installation, it is recommended that the unit be
calibrated using a sample of the media to be measured.
Relay Coil
Relay Terminal
NO to CO
6–7
De-energized
Open
Energized
Closed
Energized
Closed
De-energized
Open
De-energized
Open
56-601 Solitel Vibrating Rod Level Switch
NC to CO
7–8
Closed
Open
Open
Closed
Closed