2.2.8 Extreme Situation Actions

Warning!
If sparks, fire, smoke, or smell of burning is found at the installation site of the
product, the product must be de-energized and sent for repair

2.2.9 Troubleshooting

Fault
The
unit
fails
outputs
The unit address is not shown
in the UProg utility
16
to
control
Polling loop failure
Unit address failure or error
Unit failure
No power for executive part of
the unit
Collision
various addressable devices in
the polling loop
Possible Cause
of
addresses
Solution
Check the polling loop for
open or short circuit failure
Change the unit address for or
set it to the required value in
the range of 1 – 123
Replace the unit for a healthy
one following the instructions
of this manual
Check the power voltage at the
unit power inputs
of
Set the unit address to another
value, the value should be
between 1 and 123
Table 2.2.9.1