Akytec TRM500 User Manual
Browse online or download pdf User Manual for Controller Akytec TRM500. Akytec TRM500 2 pages. Temperature controller
1
Functional description
The TRM500 is a versatile temperature controller with switching current up to 30 A. The device has a
universal input for a wide range of resistance thermometers and thermocouples as well as a digital
input. It is provided with a relay output, an alarm output, a DC logic output. The outputs can be
configured for different tasks (see Appendix A). The controller can be quickly configured by using three
keys.
Functions:
–
On-Off or PID control (see Fig. 1)
–
Manual control
–
20 mm, 4 digit display, 2nd display optional
–
Digital input filter with an adjustable time constant
–
Custom 2-point linearization
–
Digital input (remote start/stop or setpoint change) (see Appendix D)
–
Temperature range alarm
–
Auxiliary alarm output
–
Additional logic output (SSR)
–
Configurable outputs (see Appendix A)
–
Autotuning function (see Appendix C)
–
Cold junction compensation
–
Input calibration (see Appendix E)
–
9 status LEDs
Ordering key:
30A - relay 30 A, display with 20 mm digit height
2
Safety precautions
Make sure that the device is fully disconnected from auxiliary power before
WARNING
starting any commissioning or repair work.
Connect the power supply only after the wiring has been completed.
CAUTION
DANGER
Do not use the device where it is subjected to flammable or explosive gas.
3
Specifications
Table 1 General data
Power supply
Power consumption, max.
Resistance thermometer
Accuracy
Connection circuit
Sampling time for 3-wire
Sampling time for 2- / 4-wire
Lead resistance, max.
Reference junction
Thermocouple
Accuracy
Sampling time
Lead resistance, max.
Digital input
ON, resistance max.
OFF, resistance max.
Relay outputs
OUT1
OUT2
Solid state relay OUT3
Dimensions
IP Code
Ambient temperature
Humidity
Weight
Table 2 Sensor types
Sensor
Pt50
Pt100
Pt500
Pt1000
Ni100
Ni500
Ni1000
K
J
L
N
T
S
R
B
T °C
SP+∆
SP
SP - ∆
Relay
ON
OFF
ON/OFF control
TRM500_0283_EN
© All rights reserved. Subject to technical changes and misprints.
TRM500-X
+display with 10 mm digit height
230 (96...264) V AC; 50 (47...63) Hz
5 VA
Pt50, Pt100, Pt500, Pt1000, Ni100, Ni500, Ni1000
0.25%
2-, 3-, 4-wire
0.3 s
0.2 s
15 ohm
internal
B, J, K, L, N, R, S, T
0.50%
0.2 s
100 ohm
potential free contact
70 ohm
1000 ohm
30A / 250 V AC (resistive),
20A / 30 V DC
5A / 250 V AC, 3A / 30 V DC (resistive)
0/5 V, 25-40 mA
96 x 48 x 100 mm
front IP54, rear IP20
-20...+50 °C
up to 80% (non-condensing)
approx. 160 g
Parameter
Measuring range, °C
P50
–100...+850
P100
–100...+850
P500
–100...+850
P1E3
–100...+300
N100
–60...+180
N500
–60...+180
N1E3
–60...+180
tP.K
–100...+1300
tP.J
–100...+1200
tP.L
-100...+800
tP.N
–100...+1300
tP.t
–100...+400
tP.S
0...+1750
TP.R
0...+1750
TP.B
+200...+1800
T °C
SP
0
t, s
t, s
0
t, s
t, s
PID control
Fig. 1 Control
TRM500
Temperature controller
TRM500
0000
0000
Temperature
SENSOR
sensor
DI
4
Installation and electrical wiring
Fig. 3 Mounting and dimensions
POWER
OUT1
SUPPLY
1
2
3
4
N
L1
L1
N
230 VAC
30 A, 230 VAC
20 A, 30 VDC
The maximum wire size is 0,75 mm².
5
Maintenance
Technical maintenance should be performed on the device at least every six months by maintenance
personnel and comprising the following tasks:
–
Removing dust, dirt and foreign matter from the housing.
–
Checking mounting of device
–
Checking connections
The safety guidelines in Section 2 must be observed when performing maintenance.
6
Transportation and storage
The device must be transported in closed transport boxes.
Protective measures against shocks, vibrations and humidity must be observed.
Storage temperature range -30...+60 °C.
There may be no chemically active substances in the air.
7
Package content
–
Temperature controller TRM500
–
User manual
Appendix A.
Output configuration
Output configuration
OUT1
DI
Control
Relay 30 A
OUT2
Alarm
Relay 5 A
OUT3
DI
Control
SSR
OUT2
Alarm
Relay 5 A
OUT3
Control
DI
SSR
OUT1
Relay 30 A
Alarm
OUT2
Relay 5 A
Appendix B. Displays and control elements
Display D1
TRM500
- measuring value (Operation)
- setpoint (Operation)
- control signal (Manual)
°C
- parameter group (Setup)
- parameter name (Setup)
- parameter value (Setup)
— — — error (sensor failure, CJC failure,
exceedance of the measuring range)
Display D2
- setpoint (Operation)
- measuring value (Manual)
- control signal (Manual)
- parameter name (Setup)
- parameter value (Setup)
SP1
- lit when SP1 or SP1 + SP2 is activ
- flashes when correction setpoint
SP2
- lit when SP2 or SP1 + SP2 is activ
- flashes when correction setpoint
AUTO
- lit when control is activ
- flashes when PID autituning
MAN
- lit when manual control is activ
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany
OUT2
Relay 5 A
Alarm
Alarm
Control
OUT1
Relay 30 A
Pulse
OUT3
control
SSR
Fig. 2 Block diagram
Fastenings
OUT2
OUT3
DI
SENSOR
REMOTE
5
6
7
8
9
10
11
12
13
14
RTD
SSR
2-wire
L1
N
RTD
3-wire
5 A, 230 VAC
3 A, 30 VDC
RTD
0/5 VDC
4-wire
25-40 mA
TC
Fig. 4 Electrical wiring
1
1
Alarm logic
OUT2
I
(inside range)
ON
ConF=1.U
OFF
or
t
ConF=1.
OUT2
U (outside range)
ON
II
OFF
ConF=2.U
t
or
ConF=2.
OUT2
ON
III
OFF
ConF=3.U
t
OUT1
ON
OFF
t
U.Lo U.Hi
Shotly - increasing of parameter value
TEMPERATURE TRANSMITTER
- next parameter
> 3 s - end of menu (oUt)
T
UP
Shotly - decreasing of parameter value
- previous parameter
T
NORM
T
PROG
DOWN
Shotly - selecting a menu item (Setup)
PROG
SP1
AUTO
ON
- confirmation of the modification and switch
to the next parameter (Setup)
SP2
MAN
ALARM
> 3 s - switch to the Setup mode (Operation)
- cancel modification (Setup)
T
- lit when T > upper alarm limit
UP
T
- lit when T inside the alarm limits
NORM
T
- lit when T < lower alarm limit
DOWN
ON
- lit when OUT1 or OUT3 is ON
ALARM
- lit when sensor failure and/or exceeding alarm limits
Tel: +49 (0) 511 16 59 6720 ·
Load
Load
Mounting hole
www.akytec.de