Comax AL105 Series Installation & Connection Manual - Page 4

Browse online or download pdf Installation & Connection Manual for Horn Comax AL105 Series. Comax AL105 Series 12 pages.

Construction Product Regulation
AL105.024.2 & AL105.048.2 are compliant to EN54-3:2001+A1+A2 & EN54-23:2010
VAD for use in fire detection and fire alarm systems installed in and around buildings
Alarm devices – Sounder & Beacon
Type 3R / 13, IP66, Independently tested to EN60529:1991, (IP33C Compliant to EN54-3)
Type B Product, For Indoor & Outdoor use
Observe Precautions for handling electrostatic devices
-25°C to +55°C compliant to EN54-3 & EN54-23
Cable Glands must be suitably sealed and meet minimum IP33 for EN54-3 applications
Storage Temperature: -40°C to +70°C
Maintenance – None
Units can be mounted using 2-off ø7mm holes or through the back of the housing using the
supplied gasket
Approved Tones for EN54-3 Applications:
•(Alternating Tone) 800/1000Hz @ 2Hz Alternating Tone 44
•(Rising Tone) 500/1200Hz @ 0.26Hz (3.3s on, 0.5s off) Tone 8
•(Fainting Tone) 1200/500Hz @ 1Hz Tone 2
•(Continuous Tone) 800Hz Tone 21
•(Pulsed Tone) 660Hz (150mS on, 150mS off) Tone 31
Horizontal Sound Output Max Voltage
Tone
Tone
Angle
44
8
15°
93.9
94.6
45°
99.6
101.4
75°
102.5
103.9
105°
102.5
103.9
135°
99.5
101.4
165°
94.1
94.8
Vertical Sound Output Max Voltage
Tone
Tone
Angle
44
8
15°
93.8
94.7
45°
99.6
101.4
75°
103
104.2
105°
102.6
104.2
135°
99.5
101.4
165°
94.3
94.5
The units have been tested and approved to DNVGL-CG-0339 & EN54-3:2014 incl. A1:2019
for the installation on ships in the following locations:
Temperature:
A, B, C & D (Machinery spaces, control rooms, accommodation,
bridge, inside cubicles, desks, etc..., pump rooms, holds, rooms
with no heating, Open deck, masts)
Humidity:
A & B (All locations)
Vibration:
A (Bulkheads, Beams, Deck, Bridge)
EMC:
A (All locations except Bridge & open deck)
Enclosure:
A, B & C, IP66 (Control rooms, accommodation, bridge, engine
room, open deck masts, below floor plates in engine room)
AL105.024.2 / AL105.048.2 @ 1m
(60 Vdc) LAFmax,T dB(A)
Tone
Tone
Tone
2
21
31
93.7
94
91
100.1
99.7
96.6
103.5
102.6
102
103.4
102.7
102
100.1
99.7
96.4
93.7
94.1
90.6
(60 Vdc) LAFmax,T dB(A)
Tone
Tone
Tone
2
21
31
93.5
94.3
90.2
100.1
100
96.4
103.7
103.2
101.5
103.4
102.6
101.8
100.1
99.8
96.4
93.6
94.6
89.8
Min Voltage (18 Vdc) LAFmax,T dB(A)
Tone
Tone
Tone
5
44
8
91.8
90.8
91.2
98.2
96.5
98.3
100.6
100
101.1
100.6
100
101.1
98.1
96.4
98.2
91.8
91.1
91.5
Vertical Sound Output Min Voltage
(18 Vdc) LAFmax,T dB(A)
Tone
Tone
Tone
5
44
8
91.8
90.7
91.5
98.3
96.5
98.4
100.6
99.8
101.1
100.5
100
101
98.3
96.3
98.2
91.6
91.2
91.2
The units comply with Solas 74 Chapter II-2, Regulation 7 & Chapter X,
Regulation 3 for installation on ships in the following locations:
Temperature:
Vibration:
EMC:
Enclosure:
Order Code: AL105.024.2
Voltage Range: 20-28Vdc
Nominal Voltage: 24Vdc
Max Sounder Current: P1: 125mA @ 28Vdc
Max Beacon Current: 271mA @ 20Vdc
DP-2821-CPR-0109
2821
S36282
Order Code: AL105.048.2 Voltage
Range: 42-52Vdc
Nominal Voltage: 48Vdc
Max Sounder Current: 125mA @ 52Vdc
Max Beacon Current: 160mA @ 42Vdc
DP-2821-CPR-0109
2821
S36282
Horizontal Sound Output
Tone
Tone
Tone 31
2
21
90.5
90.9
88
96.9
96.6
93.5
100.6
100.1
98.7
100.6
100.3
98.8
96.9
96.6
93.5
90.5
91.1
87.6
Tone
Tone
Tone 31
2
21
90.2
91.2
87.3
97
96.9
93.4
100.5
100.1
98.5
100.6
100
99
97
96.6
93.5
90.4
91.5
96.8
D (Location -25° to +70°C)
A (General Applications)
A (General Power Distribution Zone)
IP66, Salt mist
21
21
Tone 5
89.1
95.7
98
98.2
95.5
89.2
Tone 5
89.2
95.7
98.1
98
95.7
88.8