Advanced AX-009 Installation & Operation Manual - Page 3
Browse online or download pdf Installation & Operation Manual for Control Unit Advanced AX-009. Advanced AX-009 18 pages. Conventional zone module
1
Introduction
The AX-CZM (CAX-CZM Canadian ULC version) is Advanced's conventional zone module that can be monitored
and controlled by any ANSI/UL 864 or ULC S527 Listed fire alarm control panel (Host FACP"). The module
provides monitoring of up to eigth (8) Class B, with programmable end-of-line, or four (4) Class A conventional
zones, and has three Form C relay contacts for signalling an alarm, trouble and, if required, earth/ground fault
condition on a per module basis.
The AX-CZM module gets powered from either the HOST FACP or a regulated, power limited 24 VDC power supply
Listed for Fire Protection Signaling.
Note: The power supply power to the AX-CZM module must be a regulated, power limited 24 VDC power
supply Listed for Fire Protection Signaling.
The AX-CZM module makes use of the Advanced Software Monitoring And Real Time Power Management
(SMART-PM) techniques in order to minimize current requirements under alarm conditions across multiple zones.
This SMART-PM technology results in lower power consumption, and increased fire alarm control panel battery life.
www.advancedco.com
www.advancedco.com
Figure 1 – AX-CZM Module
3