2.3

AX-CZM Module Operating Modes

The AX-CZM module zone circuits are preset to the following operating modes:

2.3.1 Class B Mode of Operation

Zone #
1
2
3
4
5 *
6 *
7
8

2.3.2 Class A Mode of Operation

Zone #
1
2
3
4 *
* Note: These preconfigured "Non-Latching" zone circuits are not permitted by ANSI/UL864 or ULC S527.
These zones should be considered Not Connected.
2.4

AX-CZM Module Wiring

ATTENTION
OBSERVE PRECAUTIONS
FOR HANDLING
ELECTROSTATIC
SENSITIVE DEVICES
The AX-CZM module must be earth/grounded; this is normally achieved via the screws used to secure
the module to the enclosure and the enclosure being earth/grounded. Should this not be the case, a
dedicated earth/ground must be provided.
Must be
Grounded
The AX-CZM module offers eight (8) Class B or four (4) Class A conventional zones, and three (3) Form C, relay
outputs (Alarm, Trouble and Earth/Ground Fault). In addition, the AX-CZM module has a resettable input for
resetting latched zone alarm conditions.
www.advancedco.com
www.advancedco.com
Latching Input
Alarm Verification
Non-Latching
Non-Latching
Latching Input
Alarm Verification
Non-Latching
This equipment is constructed with static sensitive components.
precautions at all times when handling printed circuit boards.
earth/ground strap connected to enclosure earth/ground point.
Short Circuit = Alarm
Short Circuit = Alarm
Observe anti-static
Wear an anti-static
9