Advanced Ex-3020 Manual - Page 9
Browse online or download pdf Manual for Measuring Instruments Advanced Ex-3020. Advanced Ex-3020 20 pages. Remote status indicators
RELEASE ACTIVATED
00:00:10 Elapsed
DISCHARGE COMPLETE
(No Flow Detected)
RELEASE ACTIVATED
00:00:10 Elapsed
RELEASE CONFIRMED
DISCHARGE COMPLETE
RELEASE ACTIVATED
00:00:20 Elapsed
DISCHARGE COMPLETE
EXTRACT RUNNING
RESET ALLOWED
To reset the panel, press the RESET button on the control panel.
Reset of the Activated Condition / Release Signal.
NOTE: In accordance with EN 12094-1, the ECD shall not permit a reset until
either the RELEASED condition has been established (flow detected) or until
Section 4.12.2
after a programmable time following activation of the mechanism to release the
extinguishant.
NOTE: Depending on programming, the EXTRACT condition may persist after the panel is reset for up to 120
minutes. This will be indicated on the normal status display (Extract Running).
Released Condition.
NOTE: In accordance with EN 12094-1, the activated / release condition may be
established without the detection of a fire alarm or manual release. If the panel
detects the release of extinguishant, it will immediately indicate the released
Section 4.11
condition.
2.2.3
Hold Condition
COUNTDOWN ON HOLD
(Remove HOLD resume)
-15
When the hold button is release, the panel will resume the imminent release countdown either from the time
remaining or from the maximum time programmed.
www.advancedco.com
When the discharge is complete (either time elapsed or flow
detected) the display indicates the discharge is complete.
If confirmed by the detection of the flow of the extinguishant, the
display shows RELEASE CONFIRMED (Released Condition) and
the RELEASED LED turns ON steady.
If previously silenced, the internal buzzer will re-sound. Press the
button to silence the buzzer.
When the extinguishant has been fully released and if
automatically or manually activated, the output to control the
extract fan will be turned on.
This is indicated on the display as EXTRACT RUNNING
When the discharge is complete, the display prompts that the
panel can be reset – reset must be performed at the control panel.
If any hold button is activated, the imminent release countdown is
held for as long as the button is pressed.
The display shows the HOLD condition and the TIMER HELD LED
is illuminated.
9