Cardax Prox 125 Installation Note - Page 2
Browse online or download pdf Installation Note for Card Reader Cardax Prox 125. Cardax Prox 125 10 pages.
Cabling
Use 4 core, 0.2 mm
120 pf/m.
Maximum distance between the URI and the Prox 125 reader with this type of cable is
200m (650ft).
Removing the Facia
To remove the facia from the Prox 125 base you need a T10 Torx driver.
Use the driver to loosen the screw at the bottom of the facia.
Remove the screw.
Gently pull the lower end of the facia away from the base and then slide the facia down
and off the base.
Mounting Distance Between Proximity Readers
The distance between any 2 proximity readers must be greater than 200mm in all
directions.
2
2
(AWG 24) cabling with a maximum, nominal capacitance of
Note: You need a special cable terminating tool to connect the building cabling to
the Prox 125. The tool has a head (Part No. C861145) and handle (Part No.
C861115).
Note: Please note that 200mm in all directions includes the distance through walls.
200mm
200mm
Part number 3E0000 R3
April 2002