DPS Telecom Net Dog 82 IP Operation Manual - Page 4

Browse online or download pdf Operation Manual for Network Hardware DPS Telecom Net Dog 82 IP. DPS Telecom Net Dog 82 IP 12 pages.

DPS Telecom Net Dog 82 IP Operation Manual

Software Configuration

Local Connection
Connect a PC running terminal emulation software to
COM1 on back of the Net Dog (Fig. 7). Set your serial
port to match the data rate and word format currently
defined for the Net Dog's COM1 (factory default is
9600, n, 8, 1). Connect to the Net Dog and enter
'DPSCFG' to activate the configuration menu.
Remote Connection (Dial Up)
Set up a PC running TTY terminal emulation soft-
ware to dial the Net Dog's modem. When a connection
is established (sometimes accompanied by receipt of a
hex byte), enter 'DPSCFG' to activate the configuration
menu.
LAN Connection
In order to utilize the 10BaseT port on the Net Dog,
it must first be pre-provisioned using a remote terminal
(either dial up through the modem or directly connected
to Com 1). The LAN minimum configuration requires
setting the unit address (IP) and the subnet mask. Use of
a WAN requires that the default gateway be set.

Edit Section

Fig. 8 - To begin configuration, select E)dit from the
main menu, then s(Y)stem from the E)dit submenu.
Note: Menu Selection Hot Keys - The letter before a
parentheses right bracket ) or enclosed in parentheses ( )
is a hot key. When you type the hot key, you are taken to
that submenu. Most menus are two layers deep. Pressing
the <Esc> key brings you back to the previous level.
From the bottom level, pressing <Esc> twice returns to
the top menu.
1. Edit the System Information
Perform the following steps to configure your Net
Dog. If you change a field, the change is made when
you press <Enter>.
D-PC-295-10A-0V
May 5, 2000
Fig. 9 - to change the value of the Name field, select
N)ame and type in the desired information.
a. Select E)dit from the main menu.
b. Select s(Y)stem from the Edit submenu. The current
system field values will be displayed. The prompt
line at the bottom of the screen lists the hot keys for
each field. (Fig. 8) The field meanings are given in
Table A.
c. Select the field you want and make the changes.
Figure 9 shows an example of changing the Name
field.
d. Press <Enter>.
e. When you finish changing fields, press <Esc>.
Table A - System Submenu Fields
Field
Name
User designated name for this Net Dog
Location
Physical location of Net Dog
Contact
Person responsible for this Net Dog
Get
Community Name for SNMP requests
Set
Community Name for SNMP SET requests
Trap
Community Name for SNMP TRAPS
2. Edit the Ethernet Port Parameters
a. Select P)orts from the System submenu.
b. Select E)Port from the Ports submenu. The current
E)port field values will be displayed. The prompt
line at the bottom of the screen lists the hot keys for
each field. (See Fig. 10)
Fig. 10 - To edit the Ethernet port parameters,
select E)Port from the P)orts submenu.
4
Description
OG113939.001