COMEM DTI Instruction Manual - Page 13
Browse online or download pdf Instruction Manual for Measuring Instruments COMEM DTI. COMEM DTI 20 pages. Temperature monitoring unit

Programming of the device
Configuration diagnostic probes
This function allows to enable or to disable the control on the probes. This fun-
ctionality controls the variation of the temperature in a defined time. A flag raise
if this variation is higher than a set value.
FDC setting
FDC mode disabled
FDC mode enabled
It's necessary to indicate the maximum variation temperature:
• FDC: min 5°C or max 30°C
and after the time in which to do the control:
• FDC: min 10" or max 90" (time in seconds)
The →+ key is used to increase the values while the ←- key to decrease.
Confirm with ENTER.
Temperature configuration FDC
Min °C
Max °C
Time configuration FDC
Min in seconds
Max in seconds
Exit from the programming phase
Press the SET key or wait for about 8 seconds without to press any key to come
out of the programming phase.
T1-T2 display
FDC
FDC
T1-T2 display
FDC
FDC
T1-T2 display
FDC
FDC
T3-T4 display
Off
ON
T3-T4 display
-5°
30°
T3-T4 display
10''
90''
13