Also for Bosch FAP-OC 500Series: Installation Instructions Manual (21 pages), Instructions For Use Manual (40 pages), Installation Manual (6 pages), Installation Manual (28 pages), User Manual (48 pages), User Manual (48 pages), Installation Manual (28 pages), Use And Care Manual (44 pages), Installation Manual (32 pages), Use And Care Manual / Installation Instructions (40 pages), Quick Reference Manual (4 pages), Use And Care Manual (27 pages), Installation Manual (24 pages), Installation Manual (32 pages), Use And Care Manual (24 pages), Installation Manual (28 pages), Service Manual (41 pages), Use And Care Manual (21 pages), Installation Manual (32 pages), Service Manual (36 pages), Installation Manual (32 pages), Quick Start And Safety Manual (13 pages)

Bosch FAP-OC 500Series Product Information
Product Information 500 Series LSN Fire Detectors (EU)
7.3. Inspection Procedure for FAP−OC 500
1. Alternative
D On the central unit, switch the detector zone to be inspected into test mode. This
automatically sets the detector into revision operation and readies it for the detector
test.
. Only in revision operation the detector's individual sensors will trigger with the
corresponding test device. For an alarm, all sensors must trigger at the same time.
The C sensor is triggered using CO test aerosol, the O sensors by being covered
up. No O testing gas is required.
D Now hold the test device under the detector so that the test beaker is flush with the
trim ring and seals it tightly.
. Make sure that the test beaker does not tilt, which could cause the detector
to be lifted up and consequently become detached from its fastening.
D Spray the CO testing gas for approximately 1 sec.
. The test head must remain over the detector until the detector has been triggered.
Distribution of the CO−testing gas in the test head and therefore the sensor trigger
time can take up to 20 sec.
D Both scattered light areas are covered by the test beaker, so that both optical
sensors are also triggered at the same time.
D The detector triggers the alarm and the red alarm LED flashes.
Page 35
PI − 34.70 en
BDL−F.01U.025.876
A5.en/ 02.02.2006
ST−FIR/PRM1 / zab