Function
Function
Setting number
number
Horizontal
00 Standard
swing
24
01 Left half
airflow
direction
02 Right half
00 Standard
Cool air
tem-
01 Adjust (1)
30
perature
trigger
02 Adjust (2)
00 Standard
Heat air
01 Adjust (1)
tem-
31
02 Adjust (2)
perature
trigger
03 Adjust (3)
00 Enable
Auto
40
restart
01 Disable
00 Super low
Cool Air
Follow the
Preven-
43
setting on
01
tion
the remote
controller
00 Start/Stop
Emergency
01
stop
External
46
control
02 Forced Stop
00 All
Error
Display only
report
47
on central
01
target
remote
controller
Follow the
Fan set-
setting on
ting when
00
the remote
cooling
49
controller
thermostat
OFF
01 Stop
00 Mode 0
01 Mode 1
Switching
02 Mode 2
func-
tions for
03 Mode 3
external
60
04 Mode 4
inputs and
external
05 Mode 5
outputs
06 Mode 6
terminals
07 Mode 7
08 Mode 8
Auxiliary
00
heater con-
trol 1
Auxiliary
01
heater con-
trol 2
Heat pump
02
prohibition
Control
control
switching
61
of external
Heater selec-
tion control
heaters
03
using outdoor
tempera-
ture 1
Heater selec-
tion control
04
using outdoor
tempera-
ture 2
Default
Details
Adjust the horizontal swing airflow
direction.
(For horizontal swing equipped
models)
Adjust the cool air trigger
temperature. To lower the trigger
temperature, use setting 01. To
raise the trigger temperature, use
setting 02.
Adjust the heat air trigger
temperature. To lower the trigger
temperature by 6 degrees C, use
setting 01. To lower the trigger
temperature by 4 degrees C, use
setting 02. To raise the trigger
temperature, use setting 03.
Enable or disable automatic sys-
tem restart after a power outage.
* Auto restart is an emergency
function such as for power failure
etc.
Do not start and stop the indoor
unit by this function in normal
operation.
Be sure to operate by the control
unit, converter or external input
device.
Restrain the cold airflow with mak-
ing the airflow lower when starting
heating operation. To correspond
to the ventilation, set to 01.
Allow an external controller to start
or stop the system, or to perform
an emergency stop.
If an emergency stop is performed
from an external controller, all re-
frigerant systems will be disabled.
If forced stop is set, indoor unit
stops by the input to the external
input terminals, and Start/Stop by
a remote controller is restricted.
Change the target for reporting er-
rors. Errors can either be reported
in all locations, or only on the
central remote controller.
When set to 01, the fan stops
when the thermostat is OFF in
cooling operation. Connection of
the wired remote controller (2-wire
type or 3-wire type) and switching
its thermistor are necessary.
• Set this function when connect-
ing the VRF system to a ventila-
tor, economizer, humidifier, or
other external device.
• The connection terminal func-
tions can be changed depending
on the type of external device.
For details of the connection ter-
minal functions, see the Design
& Technical Manual.
Sets the control method for the
external heater being used. For
details of the control method, see
the Design & Technical Manual.
00 Setting 0
Operating
01 Setting 1
tem-
02 Setting 2
perature
62
switching
03 Setting 3
of external
04 Setting 4
heaters
05 Setting 5
Single
setpoint auto
00
Auto
mode
mode
68
(traditional)
type
Dual setpoint
01
auto mode
00 0°F (0°C)
01 1°F (0.5°C)
02 2°F (1.0°C)
03 3°F (1.5°C)
04 4°F (2.0°C)
Deadband
69
value
05 5°F (2.5°C)
06 6°F (3.0°C)
07 7°F (3.5°C)
08 8°F (4.0°C)
09 9°F (4.5°C)
Temperature conditions when the external heater is ON
Temperature (t) when the external heater is ON= Room temperature - set temperature
00
00
t < -5.4°F (-3°C)
01
t < -3.6°F (-2°C)
02
t < -3.6°F (-2°C)
03
t < -5.4°F (-3°C)
04
t < -7.2°F (-4°C)
05
t < -9.0°F (-5°C)
6.3.1 Indoor unit indicator lamps
4/7/9 model
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
30/36 model
OPERATION indicator lamp (green)
TIMER indicator lamp (orange)
FILTER indicator lamp (red)
6.3.2 Checking the function settings
Press and hold the "MANUAL AUTO" button on the indoor unit for 3 seconds to check
the function settings. It is necessary to disconnect the power in order to return to normal
operation mode.
(1) Indoor unit and refrigerant address indication
Indication pattern
Indicator name
Indoor unit address
OPERATION indicator lamp (Green)
ON
TIMER indicator lamp (Orange)
Address: tens place (0.5s ON/0.5s OFF)
FILTER indicator lamp (Red)
Address: ones place (0.5s ON/0.5s OFF)
• Sets the temperature conditions
when the external heater is ON.
• For the temperature conditions,
see "Temperature conditions
when the external heater is ON".
For a more detailed explana-
tion, see the Design & Technical
Manual.
Switch the setting method of
auto mode to single or dual
(cooling/heating).
For heat pump systems, it is
necessary to set the master indoor
unit (by wired remote controller).
Choose the minimum temperature
between cooling and heating
settings (deadband) for Dual
setpoint auto mode (set in No. 68).
Set value of function: 61
01
02
03
t ≤ -0.9°F (-0.5°C)
t ≤ -1.8°F (-1°C)
t ≤ -3.6°F (-2°C)
t ≤ -5.4°F (-3°C)
t ≤ -7.2°F (-4°C)
t ≤ -9.0°F (-5°C)
Indication pattern
Refrigerant address
Flash (1.0s ON/1.0s OFF)
04
En-12