AirStage ASYA24GACH Installation Manual - Page 10
Browse online or download pdf Installation Manual for Air Conditioner AirStage ASYA24GACH. AirStage ASYA24GACH 17 pages. Indoor unit
Input select
Use either one of these types of terminal according to the application. (Both types of
terminals cannot be used simultaneously.)
● Apply voltage terminal ([CNA01], [CNA03])
When a power supply must be provided at the input device you want to connect, use the
Apply voltage terminal ([CNA01], [CNA03]).
Load
resistance
*a
Load
resistance
*a
Load
resistance
*a
connected unit
*1 Make the power supply DC12 to 24V. Select a power supply capacity with an ample
surplus for the connected load.
Do not impress a voltage exceeding 24V across pins 1-2, and 1-3.
*a The allowable current is DC 5mA to 10mA. (Recommended: DC5mA)
Provide a load resistance such that the current becomes DC10mA or less.
Select very low current use contacts (usable at DC12V, DC1mA or less).
*b The polarity is [+] for pin 1 and [-] for pin 2 and 3. Connect correctly.
When connected to Apply voltage terminals of multiple indoor units with a connected unit,
be sure to make a branch outside the indoor unit using a pull box, etc. as shown on below
example.
Load
resistance
Load
resistance
connected unit
● Dry contact terminal ([CNA02], [CNA04])
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA02], [CNA04]).
*c
*c
Ch 1
Ch 2
*c
Ch 3
connected unit
*c Select very low current use contacts (usable at DC12V, DC1mA or less).
*d The wiring is different from Apply voltage terminals. Be suffi ciently careful when wiring.
When connected to Dry contact terminals of multiple indoor units with a connected unit,
insulate each indoor unit with relay, etc. as shown on below example.
En-9
DC power supply
*1
12 to 24V
DC power supply
12 to 24V
P.C.B
GND
*d
P.C.B
CNA01
*b
Input device 1
CNA03
NOTE :
When connected to multiple indoor units directly, it will cause breakdown.
Operation behavior
● Input signal type
The input signal type can be selected.
It is switched by DIP switch on the indoor unit PCB.
DIP switch [Set 2 SW2]
OFF (Factory setting)
● When function setting is "Operation/Stop" mode.
[In the case of "Edge" input]
Connector
P.C.B
Ch1 of CNA01 or CNA02
CNA01
[In the case of "Pulse" input]
P.C.B
CNA01
CNA01 or CNA02
P.C.B
* The last command has priority.
* The indoor units within the same remote controller group operates in the same mode.
CNA01
● When function setting is "Emergency stop" mode.
[In the case of "Edge" input]
Connector
Ch1 of CNA01 or CNA02
CNA02
[In the case of "Pulse" input]
CNA01 or CNA02
CNA04
* All indoor units of same refrigerant system stops when Emergency stop operates.
K1
K4
K2
K5
K3
K6
Input device 2
K1 - K6: Relay
(Device for DC Current)
Input signal type
Edge
ON
Pulse
Input signal
OFF → ON
ON → OFF
Connector
Ch1
Ch2
Input signal
OFF → ON
ON → OFF
Connector
Ch1
Ch2
P.C.B
CNA02
P.C.B
CNA02
P.C.B
CNA02
Edge
Pulse
The width of pulse
must be longer than
200msec.
Command
Operation
Stop
Input signal
Command
OFF → ON
Operation
OFF → ON
Stop
Command
Emergency stop
Normal
Input signal
Command
OFF → ON
Emergency stop
OFF → ON
Normal