4. Electrical Installation
WARNING! Install the device in currentless environ-
ments only!
Establish the electrical connection of the device according to
the technical data shown on the manufacturing label, the
following table and the respective wiring diagram.
Wiring diagrams:
1 contact
supply +
supply –
contact
2 contacts
supply +
supply –
contact 1
contact 2
Pin configuration:
M12x1 (4-pin),
Electrical
metal
connection
Supply +
1
Supply –
3
Contact 1
4
Contact 2
2
Shield
plug housing
For the electrical connection a shielded and twisted
multicore cable is recommended.
5. Initial start-up
WARNING! Before start-up, the user has to check for
proper installation and for any visible defects.
WARNING! The device can be started and operated by
authorized personnel only, who have read and under-
stood the operating manual!
WARNING! The device has to be used within the
technical specifications, only (compare the data in the
data sheet)!
6. Operation
Set point adjustment – factory set
The set points are factory set either to ordered values or to
BD|SENSORS standard:
Switching function
n/o (normally opened)
Switching mode
hysteresis mode
Switch on point
80 % FSO
Switch off point
75 % FSO
Switch on/switch off delay
off
Set point adjustment – user specific
Every DS 6 can be quickly and comfortably configured either
by means of the optionally available configuration kits
CIS 685 or CIS 686 as well as the programming device P6.
These devices can be ordered as accessories from
BD SENSORS. In the following, a short description of these
possibilities is given:
Configuration via configuration kit
The DS 6 can be connected to a PC via the programming
adapter and configured by the programming-software P-Set.
The setting of the following parameters for both set points is
possible:
- operation mode (hysteresis or window mode)
- switch-on and switch-off point
- set point negation
- switch on and switch off delay
The programming adapter is part of the programming kits
CIS 685 and CIS 686 which contains i.a. a CD-ROM with the
configuration software P-Set. All cables required for connect-
ing the pressure switch have to be plugged to the program-
ming adapter (included in scope of delivery). The user only
®
requires a Windows
PC with serial interface (CIS 685) or
USB-interface (CIS 686). Installing the configuration soft-
ware P-Set is very easy. P-Set runs on all Windows
(95, 98, ME, 2000, NT, XP, Win7).
Fig. 2 programming software
Configuration via programming device P6
V
S
The programming device P6 is simply plugged between
DS 6 and the female connector. Via two push-buttons and a
4-digit LED display, all possible settings can be realized. The
R
L
menu system of the device includes 27 menus and is easy
to handle. The following menus are – among others –
available for configuration:
- read all and store all
- operation mode
- switch-on and switch-off point
- set point negation
V
- switch on and switch off delay
S
- teach switch-on and switch-off point
R
L
- load of stored configurations
R
- storage off current configurations
L
- showing the current pressure value
- showing the limits of the measuring range
M8x1 (4-pin),
metal
Fig. 4 programming device P6
7. Maintenance
In principle, this device is maintenance-free. If desired, the
1
housing of the device can be cleaned when switched of
3
using a damp cloth and non-aggressive cleaning solutions.
4
2
With certain media, however, the diaphragm may be polluted
plug housing
or coated with deposit. It is recommended to define corre-
sponding service intervals for control. After placing the
device out of service correctly, the diaphragm can usually be
cleaned carefully with a non-aggressive cleaning solution
and a soft brush or sponge. If the diaphragm is calcified, it is
recommended to send the device to BD|SENSORS for
decalcification. Please read therefore the chapter "Service/
repair" below.
!
An incorrect cleaning can cause irreparable damages
on diaphragm. Never use spiky objects or pressured air
for cleaning the diaphragm.
8. Troubleshooting
In case of malfunction, it must be checked whether the
device has been correctly installed mechanically and electri-
cally. Use the following table to analyse the cause and
resolve the malfunction, if possible.
!
Improper action and opening can damage the device.
Furthermore, dangers may arise for the operator.
Therefore repairs on the device may only be executed
by the manufacturer!
Fault: no output signal although LEDs are working
Possible cause
line break
Fault: no output signal and LEDs are not working
Possible cause
wrong setting of the set points verify that all switch param-
Fault: device does not respond to pressure change
Possible cause
defective sensor
Fault: little shift of the output signal
Possible cause
diaphragm is calcified or
crusted
Fault: large shift of the output signal
Possible cause
diaphragm is damaged
®
PC's
9. Placing out of service
Fig. 3 programming adapter
10. Service / repair
Information on service / repair:
-
-
-
10.1 Recalibration
During the life-time of a transmitter, the value of offset and
span may shift. As a consequence, a deviating signal value
in reference to the nominal pressure range starting point or
end point may be transmitted. If one of these two phenome-
na occurs after prolonged use, a recalibration is recom-
mended to ensure furthermore high accuracy.
10.2 Return
Before every return of your device, whether for recalibration,
decalcification, modifications or repair, it has to be cleaned
carefully and packed shatter-proofed. You have to enclose a
notice of return with detailed defect description when
sending the device. If your device came in contact with
harmful substances, a declaration of decontamination is
additionally required.
Appropriate forms can be downloaded from our homepage.
Download these by accessing www.bdsensors.com or
request them:
[email protected] | phone: +49 (0) 92 35 / 98 11 0
In case of doubt regarding the fluid used, devices without a
declaration of decontamination will only be examined after
receipt of an appropriate declaration!
11. Disposal
The device must be disposed of according to the
European Directive 2012/19/EU (waste electrical
and electronic equipment). Waste equipment
must not be disposed of in household waste!
12. Warranty Terms
The warranty terms are subject to the legal warranty period
of 24 months, valid from the date of delivery. If the device is
used improperly, modified or damaged, we will rule out any
warranty claim. A damaged diaphragm will not be accepted
as a warranty case. Likewise, there shall be no entitlement to
services or parts provided under warranty if the defects have
arisen due to normal wear and tear.
13. EU Declaration of conformity / CE
The delivered device fulfils all legal requirements. The
applied directives, harmonised standards and documents are
listed in the EC declaration of conformity, which is available
Fault detection / remedy
online at: http://www.bdsensors.com.
inspect all connecting lines
Additionally, the operational safety is confirmed by the CE
of the contacts (including
sign on the manufacturing label.
the connecting plugs)
Fault detection / remedy
eters are useful and
permitted (e.g. the set
parameters must lie within
the applied pressure range)
Fault detection / remedy
please send the device for
inspection to BD|SENSORS
Fault detection / remedy
if suspected, please send
the device to BD|SENSORS
for cleaning, if possible
Fault detection / remedy
if a damage (e. g. by over-
pressure) is suspected,
please send the device
BD|SENSORS for repair
WARNING! When dismantling the device, it must
always be done in the depressurized and currentless
condition! Check also if the medium has to be drained
off before dismantling!
WARNING! Depending on the medium, it may cause
danger for the user. Comply therefore with adequate
precautions for purification.
www.bdsensors.com
Service phone: +49 (0) 92 35 98 11 0
If the device came in contact with hazardous
substances, certain precautions have to be
complied with for purification!
WARNING! Depending on the measuring medium,
deposit on the device may cause danger for the user
and the environment. Comply with adequate precau-
tions for purification and dispose of it properly.