7.0 Compressor Selections and Performance Data

7.1 CARWIN Compressor
Selection Software
The performance of the 06T/05T screw compressors can
be estimated using the CARWIN compressor selection tool.
CARWIN is a web-based application available at
https://carwin.carlylecompressor.com

7.2 Subcooler Selection

The use of mechanical subcoolers are recommended to in-
crease both the capacity and operating efficiency of the
compressors. Subcooler loads can also be estimated using
CARWIN.
Carlyle recommends sizing and piping the subcooler for
parallel flow. Parallel flow through the subcooler results in
better control of the subcooler by reducing TXV hunting.