ANDELI AJR3-1005 Instruction Manual - Page 7
Browse online or download pdf Instruction Manual for Controller ANDELI AJR3-1005. ANDELI AJR3-1005 15 pages.
3. Operation
3-1 Inspection and preparation before operating
Before operating, please check the following points.
Check if the wiring is right (especially the output terminals can not connect with power supply),
if the bypass contactor is firmly connected, and if the grounding terminal is earthed in fine condition.
Please confirm that there is not short-circuit or shortened to earth phenomenon among termin-
als and naked electriferous parts.
After the power supply is turn on, the keyboard will display
and meanwhile, the ready indication lamp brightens.
See diagram 3-1-1.
Diagram 3-1-1
3-2 Operation method
Choose the most suitable operation method according to the application requirements.
After confirm that there is no abnormal phenomenon, then you can trial run the machine. When
the product leaves the factory, it is set into keyboard with terminal and operation mode.
Press FP to set the rated power current on the nameplate of motor.
起动
停止
Press
key to start the machine and
RUN
STOP
To see if the rotation direction of motor accord with the requirements.
If the motor starting action is not satisfactory, you can adjust the set basic function in Page11.
If the starting torque of the motor is not enough, you can improve it through changing the star-
ting voltage P 0 (this way is effective when it is voltage mode) or cut-off current P 6 (this way is
effective when it is current mode).
To see if the motor rotates stably (No whistler sound and vibration).
If there isn't any abnormal phenomenon, then you can put it into formal operation.
Notice:
1. If the running of soft starter and motor is abnormal, or it displays fault code
please stop the machine immediately, and find out the cause according tofault diagnosis in
P18.
2.When the site temperature is lower than 10C, please electrified and preheat for more than 30
minutes and then start the machine.
(ready) or readiness
key to stop it.
-9-
4. Keyboard panel
4-1 Appearance of the keyboard
The keyboard has plenty of operating functions, such as functional data of confirmation and
changing for keyboard running and stopping, and various status confirmation, etc.
Indication lamp
of preparation
Function code
Up and down keys
Setting key
Confirmation key
Table 4-1-1 Functions of the operating keys
Key name
Starting key
起动
When display
RUN
1. When it is normal running, it displays
Stop key
停止
lamp lightens, press this key can stop the machine. When the machine is fully stopped, it will
STOP
display
It displays
Setting key
设置
press it again.The colon flashes, at this moment, you can press Up and DOWN keys
SET
to modify the parameter.
1. When finishing the modifying work, press this key to keep the parameter, display
sounds for two times, it means the data has been stored, press this key again or the stop key to exit.
Confirm-
确认
ation key
2. Press this key and it displays the input supply voltage
YES
3. Press this key
,
1. Enter into the menu setting, press this key to modify the parameter, (when the colon doesn't
Up and
flash
down
, press the key to modify the data code).
keys
2. During running, press this key to observe the current A, power P and overload thermal equilibrium.
When the data is larger than 999, the last radix point will be brighten, it means add 0 to mantissa.
When press a key, there has sound given from the inner soft starter, if no, it means it is inefficient
to press this key.
The keyboard can be taken off, (when operate outside the cabinet) the length of the lead should be
less than 3m.
Indication lamp
Fault indication lamp
Colon
of bypass running
READY
PASS
PERROR
Current
Ready
Running
Fault
Percent
A
Second
%
S
Data code
起动
RUN
Starting key
设置
确认
停止
SET
YES
STOP
Stop key
Main functions
, press this key, it starts, and meanwhile displays starting state
(current value) and the bypass indication
. 2. This key has reset function.
press this key and enter into the menu setting, when it displays
, refer to table 8-1 in Page14 for details
确认
and power on at the same time to reset the parameter back to the factory value.
YES
, press the key to modify the function code. When the colon flashes
-10-
.
,
and give