Anden DH4AS35 Quick Start Manual

Browse online or download pdf Quick Start Manual for Humidifier Anden DH4AS35. Anden DH4AS35 4 pages. Steam humidifier

Anden DH4AS35 Quick Start Manual
1
Choose a location in a
conditioned space
Place outside the grow room if possible. The capacity of the
humidifier is reduced by the length of the steam hose or pipe due
to condensation. The maximum recommended length of steam
hose is 6 feet. Use hard pipe insulated with 1" thick insulation
rated for 212°F or higher for lengths greater than 6 feet. If 6-foot
steam hose does not reach from humidifier to dispersion tube,
splice in 1" copper pipe using 3/4" x 1" reducing coupling.
See Installation Manual for more details.
STEAM HOSE OR PIPE.
INSULATE PIPE WITH
1" FIBERGLASS
TO REDUCE
STEAM LOSS.
90° LONG
SWEEP OR TWO
45° ELBOWS
Install dispersion tube
• The steam tubelets must face up
regardless of the airflow direction
in the duct. The plate is labeled
"UP" to indicate proper orientation.
• On horizontal duct runs, install the
dispersion tube low in the duct.
On vertical duct runs, center the
tube on the duct.
AS35 Steam Humidifier
Quick Start Guide
TUBELETS
5" MINIMUM
DISPERSION
TUBE
DUCT
* PITCH STEAM HOSE DOWN
FROM DISPERSION TUBE
TO HUMIDIFIER:
2"/FT (15%) MINIMUM
WHEN USING STEAM HOSE.
1/4"/FT WHEN USING
HARD PIPE.
90-1521
Duct location and
absorption distance
Absorption distance is the unobstructed straight line distance
needed for steam to be fully absorbed.
• Determine absorption distance based on the lowest air
velocity that the system will see (refer to table below).
• Locate dispersion tube in a straight section of duct, far
enough upstream of any obstructions or bends in the duct.
AIRFLOW
SUPPLY DUCT
ABSORPTION DISTANCE
Recommended
Absorption
Tonnage
per CFM
Distance
5 ton
12 inches
2000 CFM
10 ton
6 inches
4000 CFM
3
NOTE: If the dispersion tube is mounted on insulated ductwork,
make sure the insulation is not more than 2" thick at tube location.
2
ABSORPTION
DISTANCE
C E N T E R
C E N T E R
90-2510
1