installation
duct mounted installation
1. Choose a location in the duct that
is downstream of the humidifier
steam distribution unit. Make sure
the humidistat mounting location is
close enough to plug in the sensor.
install the sensor a minimum
of 6" ahead of or a minimum
15" after a change in air flow
direction or obstruction in the
duct. do not install duct sensor
near outdoor air intake.
2. Drill a 1/2" holes in the duct to
place the sensor. Use a sheet
metal screw (D) to attach the sen-
sor to the duct. Arrows in the duct
mount sensor indicate the direction the air flow should pass over the
sensor for optimal measurements.
3. Mount the humidistat display to a wall or duct in a convenient
location that allows easy adjustment to the settings. To mount the
humidistat, remove the back plate and install with screws (D or E)
through the mounting holes.
4. CAUTION: do not plug or un-plug the duct sensor with power
applied to the humidistat, the humidity sensor will break. Plug the
duct sensor into the humidistat. Pay close attention to the orienta-
tion of the plug or permanent damage will occur to the sensor. See
Figure 3 for proper orientation of the duct sensor plug. Place the
hook of the red plug up and away from the humidistat display board
and push onto the white connector located in the bottom left corner
of the humidistat display board. The wire colors also market on the
circuit board and match the correct orientation of the plug wires.
CAUTION: Turn off power before plugging or un-plugging duct
sensor. Do not plug or un-plug the duct sensor with power applied to the
humidistat, the sensor will break.