Anderson VFS82 Operation Manual - Page 13

Browse online or download pdf Operation Manual for Burner Anderson VFS82. Anderson VFS82 16 pages.

10. Troubleshooting Procedures

Problem
Cannot initiate a
Air pressure switch has not made contact
start sequence
High gas pressure switch has activated.
Low gas pressure switch has activated
Purge cycle not completed.
Malfunction of the flame safeguard system
(e.g., flame sensor failure or electrical noise in
the sensor line). No power to the control unit.
Main power is off.
Start-up sequence
There is no power to the ignition transformer
runs but burner
does not light
No power to ignition transformer or wire
broken between transformer and sparker
The igniter needs cleaning
The igniter is not correctly grounded to the
burner
Too much gas: Improper gas valve train
sequence
Too much gas: Manual gas butterfly valves have
been opened too far
Too much gas: Gas pressure out of the main gas
pressure regulator is too high
Not enough gas: The gas pressure out of the
main gas pressure regulator is too low
Anderson Thermal Soluions(Suzhou)Co., Ltd
Anderson Thermal Solutions – VFS82 Burner Operation Manual
Possible Cause
11
Solution
Check air pressure switch adjustment.
Check air filter.
Check blower rotation.
Check outlet pressure from blower.
Check incoming gas pressure, adjust if
necessary.
Check pressure switch setting and operation
Check flame safeguard system or purge timer.
Have a qualified electrician troubleshoot and
correct the problem.
Be sure the main power to the system is
switched to the "on" position.
Restore the power to the ignition transformer
Check electrical connection between the
transformer and the sparker.
Clean the igniter
Clean the threads on the igniter and the
burner. NOTE: Do not apply grease to the
threads on the igniter
Verify solenoid valve is down-stream of
proportionator
Check pressures and settings against start-up
report and adjust as necessary
Check start-up setting. If necessary, remove
the regulator and investigate.
Check start-up setting. Check the regulator
and adjust if necessary