8. INSTALLATION
1.
Remove cover by looseing the screw on the
bottom of the unit.
4.
Return the printed circuit board that was
removed in "3" above, to its original position
and then tighten the screw.
Do not touch the
MW DETECTOR.
9. FCC STATMENT
This equipment has been tested and found to comply with the limits for a Class B digital device. Pursuant to Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful interference in a residential installation. This equipment generates, used and can radiate radio frequency energy
and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, these is no guarantee that
interference will not occur in a particular installation. If this equipment dose cause harmful interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by one more of the following measures:
* Reorient or relocate the receiving antenna.
* Increase the separation between the equipment and receiver.
* Connect the equipment into and outlet on a circuit different from that to which the receiver is connected.
* Consult the dealer or an experienced radio/TV technician for help.
The user should not modify or changes this equipment without written approval from ALEPH.
Modification could void authority to use this equipment.
10. TROUBLE SHOOTING
Problem
Dose not power up.
LED's indicator does not turn on.
LED indicator does not blink.
MW LED stays lit continously.
11. TESTING and MAINTENANCE
Inspection:
An inspection of this unit should be made
periodically, consisting of, but not limited to, all
mounting, wiring, and the condition of all
components.
Cleaning:
Clean the plastic parts of this unit with a soft, clean,
dump cloth.
Testing:
This unit should be tested at least once per year for
proper performance and operation.
Note:
This unit is designed to be incorporated into an
overall alarm system. As it is part of the system
ALEPH cannot assume responsibility for theft or
damage if the system fails to operate.
2.
Remove the printed circuit board by loosing
the screw on it.
Do not touch the
MW DETECTOR.
5.
Wiring Diagram
SPARE
N.O.
TAMPER
N.O.
N.C.
N.C.
All wiring must be in accordance with
NEC,NFPA70.
Cause
No input power or voltage is too low.
Polarity connection may be reversed.
LED mode selection switch #4 is OFF.
Unsuitable adjusting the detection zone.
Mode selection switch #5 is PIR MODE only.
MW DETECTOR operation trouble.
If you have any questions about this product please contact ALEPH or
your nearest dealer.
NIPPON ALEPH CORPORATION
1-28-52 Komaoka, Tsurumi-ku, Yokohama, Japan
Tel: (045)575-1111 Fax: (045)580-1676
URL http: //www.nippon-aleph.co.jp/
ALEPH INTERNATIONAL CORPORATION
1026 Grisworld Avenue, San Fernando, California 91340, U.S.A.
Tel: (818)365-9856 Fax: (818)365-7274
URL http: //www.aleph-USA.com/
ALEPH EUROPE LTD.
1 Newton Close, Park Farm Industrial Estate, Wellingborough, Northhamptonshire,
NN8 3UW, England
Tel: (0933)679600 Fax: (0933)401165
URL http: //www.alepheurope.com/
ALEPH Central - Eastern Europe, LLC
Lopuszanska 53/010 Warsaw, Poland
Tel: +48 22 868 0414 Fax: + 48 22 868 0413
URL http: //www.aleph-cee.com/
3.
Use the two screws supplied with the unit to
attach the unit to the wall or corner.
6.
To attach cover, hook upper part and push
+ −
down, then tighten screw at bottom of the
unit.
POWER
Remedy
Supply the proper voltage (9.5 to 16 VDC).
Adjust the polarity.
Adjust mode selection switch #4 to LED ON.
Adjust the detection zone.
Mode selection switch #5 is DUAL MODE.
Mode selection switch #5 is PIR MODE only.
e-mail: [email protected]