Compac MR160P Installation And Setup Instructions - Page 13

Browse online or download pdf Installation And Setup Instructions for Dispenser Compac MR160P. Compac MR160P 18 pages.

Calibration (K-Factor)

11.

Setting the K-Factor

11.1
K-Factor is a proportional calibration factor of litres dispensed per revolution of the meter.
To calibrate the dispenser/pump, dispense fuel into a certified measuring container, and
compare the display value with the amount dispensed.
Example:
Display shows 10.00
True volume
To calculate the correct 'K' Factor from the information above; firstly record the existing
'K' Factor.
New
'
K'
Change the existing 'K' Factor to this new value.

Sealing the K-Factor switch

11.2
After calibration the K-factor switch should be sealed as shown
\\Cilaklfs1\shrdata\Masters\Installation Sheets\Master & Premier\MR160P Installation
20.00
Factor
Existing
'
K'
Existing
'
K'
Existing
'
K'
Sheet.doc
Page 13 of 18
Dispensed
Amount
Factor
Displayed
Amount
20.00
Factor
10.00
Factor
2