AirTech ACR35CV Installation And Wiring Instructions - Page 5
Browse online or download pdf Installation And Wiring Instructions for Fan AirTech ACR35CV. AirTech ACR35CV 13 pages.
Menu
If the buttons are pressed the display goes from prism mode to direct view mode and
menu activated. If the buttons are not pressed for 30 seconds the display reverts to
prism mode.
The
(Up) button is used to increase the value of a
setting, the
(Down) button is used to reduce the value
of a setting and the
advance to the next menu item.
The fan has the following 'menu' modes:
Standard (press any button from normal runtime -
Advanced/Engineer (hold
Data-logger readout (hold
Standard settings:
Display
Configuration
text
Option
r‐n
Rotate display
trI
Trickle speed
adjustment
bSt
Boost speed
adjustment
b15
Boost Overrun
time
h70
Humidity level
trigger
F‐0
Fan Control Mode F‐0 = CV disabled, wall /
c‐n
Comfort mode
unl
Enable / disable
lock code
‐‐‐
Menu lock code
cod
*If "0" is selected, the fan switches to Intermittent mode.
(Mode/Set) button is used to
+
for 5 seconds from the standard menu)
for 5 seconds from standard menu)
Selections
r‐Y = display rotated
100mm: 0*, 5 to 30 l/s (Max limited by Boost Selection)
100mm: 6 to 35 l/s (Min limited by Trickle Selection)
b0 to b30 – 0 to 30 minutes (0 disables overrun)
h40 to h90 ‐ 40% to 90% relative humidity
window installation
c‐n = normal LS overrun
loc ‐ lock code enabled
Up / down selects current digit, X moves to next digit.
To change the lock code when "cod" is displayed select the up/down
buttons to select a digit then select X to move on to the next digit.
r‐n = display normal
F‐1 = CV disabled,
ducted installation
c‐Y = comfort mode
unl ‐ lock code disabled
(unlocked)
)
Default
9l/s
15 l/s
70%
F‐2 = CV Constant
Volume enabled
10c
r‐n
15
RH
F‐0
c‐n
unl