Compact Electric CDMR-61 User Manual - Page 13
Browse online or download pdf User Manual for Relays Compact Electric CDMR-61. Compact Electric CDMR-61 13 pages. Digital line monitoring relay
Line Monitoring Relay CDMR-61
Par.
Funct.
No.
43
f<
47
f<
48
f<
Return Delay
44
f<
42
f<
Output Relay
36
f>
40
f>
41
f>
Return Delay
37
f>
35
f>
Output Relay
29
f>>
33
f>>
34
f>>
Return Delay
30
f>>
28
f>>
Output Relay
57
Vs>
58
Vs>
61
Vs>
BlockingTime
62
Vs>
56
Vs>
Output Relay
71, 73
Asy
75
Asy
76
Asy
Return Delay
72, 74
Asy
70
Asy
Output Relay
99
Psy
103
Psy
104
Psy
Return Delay
100
Psy
98
Psy
Output Relay
77
SEQ
Output Relay
79
General
78
Negated Relays
80
Ext. Blocking U,f
83
U< Trip Logic
82
Selfmonitor. ->K5
123
Security Code
CDMR61e_man_A1.doc
/ User Manual
Setting
Parameter
range
Trip Frequ
[45 -65] Hz
Trip Delay
[0.06 - 60] s
[0.06 - 60] s
Hysteresis
[0.00 – 5.00] Hz
K1 ..K5
Trip Frequ
[45 -65] Hz
Trip Delay
[0.06 - 60] s
[0.06 - 60] s
Hysteresis
[0 – 5.00] Hz
K1 ..K5
Trip Frequ
[45 -65] Hz
Trip Delay
[0.06 - 60] s
[0.06 - 60] s
Hysteresis
[0 – 5.00] Hz
K1 ..K5
Trip Angle
[1- 30] °
Trip Logic
[0 - 9]
[1 - 20] s
Pulswidth
[1 - 20] s
K1 ..K5
TripVoltage
[1 - 50%] Un
Trip Delay
[0.04 - 60] s
[0.04 - 60] s
Hysteresis
[0 - 20%] Un
K1 ..K5
Trip Angle
[1.0 - 10.0] °
Trip Delay
[0.04 - 60] s
[0.04 - 60] s
Hysteresis
[0 - 5.0] °
K1 ..K5
K1 ..K5
Mains
3- /4-wire
K1 ..K5
0, 1, 2
on / off [0/1]
on / off [0/1]
[ 0 - 999 ]
Default
Customers
setting
setting value
49.80 Hz
0.12s
0.12s
0.05 Hz
--
51.00 Hz
0.12s
0.12s
0.05 Hz
--
52.00 Hz
0.12s
0.12s
0.05 Hz
--
8 °
8
(L1+L2+L3)
5 s
1 s
--
20 % Un
0.1s
0.1s
10%
--
4°
0.1s
0.1s
1°
--
--
4-wire
--
0
off
off
000
Page 13
Dim
Hz
s
s
Hz
Hz
s
s
Hz
Hz
s
s
Hz
°
s
s
V
s
s
V
°
s
s
°