Daikin VRVIII Series Technical Data Manual - Page 13

Browse online or download pdf Technical Data Manual for Air Conditioner Daikin VRVIII Series. Daikin VRVIII Series 20 pages. Air conditioning systems bs box
Also for Daikin VRVIII Series: Technical Data Manual (20 pages), Technical Data Manual (18 pages), Technical Data Manual (11 pages)

Daikin VRVIII Series Technical Data Manual
6
Dimensional drawing & centre of gravity
6 - 1 Dimensional drawing
FXMQ-P
FXMQ100,125P
• REMOTE CONTROL DIMENSIONS
40-ø 4.7 hole
(Suspention bolt position)
(All around)
Air Outlet
• REMOTE CONTROL HOLDER
INSTALLATION PROCEDURE
(INSTALLATION TO WALL SURFACE)
Liquid crystal remote
700 or more
control (wireless)
(service space)
Inspection hatch 450 or more
Air outlet
Remote control holder
Ceiling
142
• Indoor Units • CONCEALED CEILING UNIT • FXMQ-PVE
Transmitting part
48-ø 4.7 hole
(All around)
Air Inlet
79
• Service space for ceiling installation
300 or less
Air Inlet
(Note 2)
N
OTE
1
Do not install more than 3 receivers in the vicinity of one another.
Floor surface
With 4 or more units, there is always the possibility of malfunction.
®
• VRV
Systems • Indoor Units
NOTES
• RECEIVER DETAIL
1
Location of MANUFACTURE'S LABEL:
Control box surface
2
Mount the air filter at the suction side.
(Select its colorimethod (gravity method) 50% or
more)
3
Do not locate things should not be wet under the
indoor unit.
Dews may droop when humidity reaches over 80%,
or a drain gets stuck, or air filters are not clean.
Inspection hatch
20 - 8x12 oblong hole
(All around)
View
(From the Air Outlet)
20 - 8x12 oblong hole
(All around)
(From the air inlet)
4
Space for Service Works
According to any one of below 1) - 3), secure a space for service works, such
as, checking and maintenance of control box and drain pumps, etc.
1) One inspection hatch (450x450) on the control box side and a space of
300mm or more under the unit. (Fig.A)
2) One inspection hatch (450x450) on the control box side and 2 (two)
inspection hatches under the unit (Arrow view B-1)
3) 3 (three) inspection hatches under the unit and the control box. (Arrow view B-2)
<Inspection hatch>
(Ceiling opening)
Control box
Control box
Ceiling
Ceiling
Inspection hatch
Inspection hatch (°450)
Inspection hatch (450mmx450mm)
Control box
Control box
Inspection hatch 3
2 - 5x9 Slot
Control box
Air
Air
outlet
inlet
Fig. A
or more
Inspection hatch 2
View B-1
View B-2
12 Drain hose (accessory)
O.D. ø 32 (outlet)
11 Socket (for maintenance)
VP25 (O.D. ø 32 /I.D. ø 25)
10 Hook
For M10
9 Air suction flange
8 Air discharge flange
7 Power supply connection
6 Interunit wiring connection
5 Control box (inside)
4 Ground terminal (in control box)
M4
3 Drain pipe connection
VP25 (O.D. ø 32 /I.D. ø 25)
2 Gas pipe connection
ø 15.9 flale connection
(Ceiling opening)
1 Liquid pipe connection
ø 9.5 flale connection
ITEM PART NAME
REMARK
Switch box
(Field supplied parts)
3D007898B
3D060162